11.6.4. CS-F28DB4E5 CU-YL28HBE5
Operation mode : Heating
HP
Outdoor Temp
(WB)
15
-15
1.99
-10
2.09
-6
2.22
1
2.30
6
2.42
10
2.57
15
2.77
18
3.01
Indoor Temp (DB)
20
25
2.06
2.26
2.16
2.36
2.30
2.50
2.38
2.58
2.49
2.69
2.64
2.84
2.84
3.04
3.08
3.28
LP
Outdoor Temp
(WB)
-15
0.20
-10
0.22
-6
0.25
1
0.36
6
0.61
10
0.64
15
0.73
18
0.90
109
Indoor Temp (DB)
15
20
0.27
0.29
0.32
0.43
0.68
0.71
0.80
0.97
25
0.36
0.37
0.41
0.52
0.77
0.80
0.88
1.06