Mitsubishi city multi PKFY-08NAMU-A Technical & Service Manual page 15

Split-type, heat pump air conditioners
Table of Contents

Advertisement

4-2. Electrical parts specifications
PKFY-08NAMU-A
Model
Symbol
Parts name
Room temperature
thermistor
Liquid pipe thermistor
Gas pipe thermistor
Fuse
(Indoor power board)
Fan motor
(with thermal fuse)
Fan motor capacitor
Vane motor
(with limit switch)
Linear expansion valve
Power supply terminal
block
Transmission terminal
block
TH21
Resistance 30˚F/15.8k", 50˚F/9.6k", 70˚F/6.0k", 80˚F/4.8k", 90˚F/3.9k", 100˚F/3.2k"
TH22
Resistance 30˚F/15.8k", 50˚F/9.6k", 70˚F/6.0k", 80˚F/4.8k", 90˚F/3.9k", 100˚F/3.2k"
TH23
Resistance 30˚F/15.8k", 50˚F/9.6k", 70˚F/6.0k", 80˚F/4.8k", 90˚F/3.9k", 100˚F/3.2k"
FUSE
MF
C
MV
LEV
TB2
TB5
OC292-13
PKFY-08NAMU-A
250V 6A
4-Pole Output 8W / PS4N8
1.2µF
440V
MSFBC20A03 DC12V
DC12V Stepping motor drive
Port [3.2 (0~2000pulse) EDM-402ME
(L1, L2,GR) 250V 20A
(M1, M2) 250V 10A