Configuration

The default settings of the detector meet most application needs. These settings
can be customized to meet additional requirements. Customizing the Nano
detector requires changing the settings of the eight segments of the
configuration DIP switch (Figure 12) mounted on the main PCB. See Table 4
below and the paragraphs following the table to determine the proper switch
setting for the application.
Figure 12: Configuration DIP switch
Table 4: DIP switch settings
Setting
Switch
Set detector
sensitivity
Alarm factor 6
OFF
Alarm factor 7
ON
Alarm factor 8
OFF
Alarm factor 9
ON
Classifire On
Fixed alarms
Flow limit offset
±40
±20
±5
±3
Flow delay
240 seconds
30 seconds
Input select
PSU Fault
ClassiFire
Override
Auto calibration
Enable
Disable
The settings in bold text are the factory default settings.
Note:
LaserSense Nano Aspirating Smoke Detector Installers Handbook
Switch
Switch
1
2
3
OFF
OFF
ON
ON
OFF
ON
Chapter 2: Installation and configuration
Switch
Switch
Switch
4
5
6
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
ON
Switch
Switch
7
8
OFF
ON
OFF
ON
23