- Design and install the product so that fluid always
fills the detection passage.
1, If the product is used when the detection passage
is not filled, correct detection signal is not output
from the electrodes, making correct measurement
impossible.
For vertical mounting, apply fluid from the bottom
to the top.
applying fluid from the top to the bottom, leading
to operation failure.
(There should not be a problem as long as the
fluid passage is completely filled with fluid)
2. When the product is mounted vertically, place the
display perpendicular to the floor (to place the
electrodes on the right and the left) to prevent
bubbles from occurring.
After installation, the flow direction can be
changed by setting.
Refer to "Operation" in page 46 for details for
setting.
Above
Fluid passage
Down
Not susceptible to bubbles
Bubbles may be generated when
Above
Electrode
Display
Down
Susceptible to bubbles
-7-
No.LV50***-OMQ0004-B