Galleon 6KRT User Manual page 29

6k/10k rack/tower online ups
Table of Contents

Advertisement

Fault
04: Bus Unbalance
Fault
11: Inv Start Fail
Fault
12: Inv Volt High
Fault
13: Inv Volt Low
Fault
14: Output Short
Fault
1A: NegPower
Fault
21: Batt SCR Short
Fault
24: Inv Rly Short
Fault
35: Para Comm Fail
Fault
36: OP.I Unbalance
Fault
41: Over Temp
Fault
42: CPU Comm Fail
Fault
43: Over load
1) The load is special or abnormal,
so the internal positive and
negative DC bus voltages are
unbalanced.
2) The internal converter failed.
The internal inverter failed, so the
inverter voltage could not start up
correctly.
The internal inverter failed, so the
inverter voltage is too high.
The internal inverter failed, so the
inverter voltage is too low.
Short circuit occurs on the UPS
output.
UPS output power is negative. It
means there is energy feedback
into the internal of UPS from
output. It may be caused by
regenerative load or current control
failure in the parallel system.
The internal battery SCR is failed
and short.
The internal inverter relay is stick to
short or the SCR of STS (Static
Transfer Switch) is short.
Parallel cable for communication is
not connected well in the parallel
system.
The output current is extremely
unbalanced between the paralleled
UPSs or there is an error in the
parallel system.
The internal temperature is too
high and reach the fault level
(shutdown):
1) Maybe the environment is hot.
2) Maybe the fan is blocked or
failed.
3) Maybe ventilation is blocked by
the wall or other goods.
4) Load is too heavy.
Internal
communication
between CPUs.
Overload
time
is
specification and the UPS shuts
down automatically.
Contact the dealer.
Contact the dealer to repair.
Contact the dealer to repair.
Contact the dealer to repair.
Remove short circuit.
Contact the dealer.
Contact the dealer to repair.
Contact the dealer to repair.
Connect the parallel cable well.
Contact the dealer to repair.
1) Make
temperature not over 40ºC.
2) Make sure the fan is OK.
3) Make sure ventilation is well.
4) Remove
possible.
failure
Contact the dealer to repair.
out
of
the
Remove excess loads from UPS
output and restart it.
sure
the
ambient
some
loads
if