Galleon 6KRT User Manual page 28

6k/10k rack/tower online ups
Table of Contents

Advertisement

Warning
0D: Over Temp
Warning
0E: Charger Fail
Warning
10: IP Fuse Open
Warning
33: Overload 3Times
Warning
3A: Maintain Open
Warning
3F: Para Protect
Fault
01: Bus Start Fail
Fault
02: Bus Over
Fault
03: Bus Under
The internal temperature is too
high and reach the warning level:
1) Maybe the environment is hot;
2) Maybe the fan is blocked or
failed;
3) Maybe ventilation is blocked by
the wall or other goods.
4) Load is too heavy.
Charger failed.
Input fuse on the power stage
board is burnt.
Locked in bypass after overload 3
times in 30 minutes.
EMBS port is open or the maintain
switch sensor (connected to EMBS
port) is trigged. (The UPS is
transferred to bypass).
Parallel cable is still not connected
well when restart after the parallel
system is fault because of parallel
communication failure. (When this
warning appeared, the UPS could
not start up because it is system
protection for parallel system)
The internal converter failed, so the
DC bus voltage could not be
boosted correctly.
1) DC bus voltage is too high
because of mains input or load
transient current.
2) The internal converter failed.
The internal converter failed, so the
DC bus voltage is too low.
1) Make
sure
temperature not over 40ºC.
2) Make sure the fan is OK.
3) Make sure ventilation is well.
4) Remove
some
possible.
Contact the dealer for repair.
Check and replace the input
fuse.
Remove excess loads from UPS
output first. Then, shut down
the UPS and restart it.
If
the
EMBS
short-circuited, the warning will
disappear.
1) If the system is still needed
to be operated in parallel
mode, please connect the
parallel cable well. And,
choose "Para Unlock" in
control menu to remove the
warning. Then, the UPS
could start up.
2) If the UPSs in the system are
separated to single UPS,
please disconnect the output
to other UPSs and choose
"Para Unlock" in control
menu
to
remove
warning. Then, the UPS
could start up.
NOTE: Be careful to check
the UPS operation mode
(parallel or single) and the
connections. If the parallel
cable is not connected in the
parallel mode, the UPS may
be damaged.
Contact the dealer to repair.
1) Shut down and restart the
system to see if it happens
again.
2) Contact the dealer to repair.
Contact the dealer to repair.
ambient
loads
if
port
is
the