Download Print this page

Important Consideration; Mounting Location - Gentex 7109CS Installation Instructions Manual

Photoelectric type commercial & commercial residential smoke alarms for the hearing impaired, ac powered with 9v battery backup

Advertisement

other health and supervisory care and retirement homes. Please
refer to NFPA 101,The Life Safety Code, and NFPA 72 for smoke
alarm requirements for fire protection in buildings not defined as
"households."
Installing smoke alarms may make you eligible for lower insurance
rates, but smoke alarms are not a substitute for insurance.
Visual signals are only one method of alerting the hearing impaired
to a fire. The visual signal may not awaken all hearing impaired
individuals. The visual signal must be in the line of sight of the
individual to be seen and effective. Home owners and renters should
continue to insure their lives and property.
PLACEMENT OF SMOKE ALARMS
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE
WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S
STANDARD 72 (National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269).
For your information, the National Fire Protection Association's
Standard 72, reads as follows:
NFPA 72, 2010 Edition, Chapter 29, Section 29.5.1 Required
Detection, states the following:
29.5.1.1 Where required by applicable laws, codes or standards for a
specific type of occupancy, approved single and multiple-station
smoke alarms shall be installed as follows:
1) In all sleeping rooms and guest rooms
2) Outside of each separate dwelling unit sleeping area, within 6.4m
(21ft) of any door to a sleeping room, the distance measured along a
path of travel
3) On every level of a dwelling unit, including basements
4) On every level of a residential board and care occupancy (small
facility), including basements and excluding crawl spaces and
unfinished attics
5) In the living area(s) of a guest suite
6) In the living area(s) of a residential board and care occupancy
(small facility)
29.5.1.2 Where the area addressed in 29.5.1.1(2) is separated from
the adjacent living areas by a door, a smoke alarm shall be installed in
the area between the door and the sleeping room, and additional
alarms shall be installed on the living area side of the door as
specified by 29.5.1.1 and 29.5.1.3.
29.5.1.3 In addition to the requirements of 29.5.1.1(1) through
29.5.1.1(3), where the interior floor area for a given level of a dwelling
unit, excluding garage areas, is greater than 93m
alarms shall be installed per 29.5.1.3.1 and 29.5.1.3.2.
29.5.1.3.1 All points on the ceiling shall have a smoke alarm within a
distance of 9.1m (30ft) travel distance or shall have an equivalent of
one smoke alarm per 46m
(500ft
2
interior square footage of floor area per level by 46m
29.5.1.3.2 Where dwelling units include great rooms or vaulted/
cathedral ceilings extending over multiple floors, smoke alarms
located on the upper floor that are intended to protect the aforemen-
tioned area shall be permitted to be considered as part of the lower
floor(s) protection scheme used to meet the requirements of
29.5.1.3.1.
The installation of additional alarms of either the smoke, heat or
CO type should result in a higher degree of protection. Adding alarms
to rooms that are normally closed off from the required alarms
increases the escape time because the fire does not need to build to
the higher level necessary to force smoke out of the closed room to
the required alarms. As a consequence, it is recommended that the
householder consider the installation of additional fire protection
devices. However, it should be understood that NFPA 72 does not
require additional smoke alarms over and above those called for in
Figures 1, 2, 3 and 4 where required smoke alarms are shown.
Figure 1
Figure 1:
A SMOKE ALARM MUST BE LOCATED ON EVERY
LEVEL OF DWELLING UNIT, INCLUDING BASEMENT, WITHIN
EACH SLEEPING ROOM AND OUTSIDE SLEEPING AREAS.
Where to Locate the Required Smoke Alarms. The major threat
from fire in a dwelling unit occurs at night when everyone is asleep.
Persons in sleeping areas can be threatened by fires in the remainder
(1000ft
), smoke
2
2
) is evaluated by dividing the total
2
(500ft
).
2
2
of the unit; therefore, smoke alarms are best located in each bedroom
and between the bedroom areas and the rest of the unit as shown in
Figure 2.
Figure 2
Figure 2: A SMOKE ALARM MUST BE LOCATED BETWEEN THE
SLEEPING AREA AND THE REST OF THE DWELLING UNIT AS
WELL AS IN EACH BEDROOM.
In dwelling units with more than one bedroom area or with
bedrooms on more than one floor, more than one smoke alarm is
required, as shown in Figure 3.
Figure 3
Figure 3: IN DWELLING UNITS WITH MORE THAN ONE SLEEPING
AREA, A SMOKE ALARM MUST BE PROVIDED TO PROTECT
EACH SLEEPING AREA IN ADDITION TO SMOKE ALARMS
REQUIRED IN BEDROOMS.
In addition to smoke alarms outside of the sleeping areas and in
each bedroom, NFPA 72 requires the installation of a smoke alarm on
each additional level of the dwelling unit, including the basement.
These installations are shown in Figure 4. The living area smoke
alarm should be installed in the living room or near the stairway to the
upper level, or in both locations. The basement smoke alarm should
be installed in close proximity to the stairway leading to the floor
above. Where installed on an open-joisted ceiling, the smoke alarm
should be placed on the bottom of the joists. The smoke alarm should
be positioned relative to the stairway so as to intercept smoke coming
from a fire in the basement before the smoke enters the stairway.
Figure 4
Figure 4: A SMOKE ALARM MUST BE LOCATED ON EACH LEVEL
IN ADDITION TO EACH BEDROOM.

IMPORTANT CONSIDERATION

NFPA 72, 2010 Edition, Chapter 29, Section 29.8.1.4(5)(b)
states: "Smoke alarms installed in one- and two-family dwellings
shall not remain in service longer than 10 years from the date of
manufacture." Smoke alarms should be replaced for the
following reasons:
Dust, dirt, and other environmental contaminants can affect your
smoke alarm over a prolonged period.
Fast changing industry consensus standards and codes on all
smoke alarms make it advisable to periodically upgrade your device
to maximize life safety.
Assurance that your smoke alarm needs are kept abreast with the
constantly improving electronic technology.
Smoke alarms are recognized as one of the lowest cost ways to
protect dwelling inhabitants against the danger of fire(s). It makes
good common sense to periodically replace and update your smoke
alarm that contributes so much to life safety.

MOUNTING LOCATION

Ceiling location (CS & CSX only) - smoke alarm should be mounted
as close as possible to the center of a hallway or room.
Wall location-locate the top of the smoke alarm not more than 12
inches from the ceiling and must be within 16 feet of pillow. Observe
Figures 1, 2, 3, & 4 are reprinted with permission from NFPA 72, National Fire Alarm Code®,
Copyright ©2002, National Fire Protection Association, Quincy, MA 02169. This reprinted
material is not the complete and official position of the National Fire Protection Association on
the referenced subject which is represented only by the standard in its entirety. National Fire
Alarm Code® and NFPA 72® are registered trademarks of the National Fire Protection
Association, Inc., Quincy, MA 02169.
550-0094
Page 7-3

Advertisement

loading

This manual is also suitable for:

7109ls7109csx7139cs7139ls