Smith 70-195 Installation And Operation Instructions Manual page 5

Gas-fired residental boilers
Table of Contents

Advertisement

4. Outdoor Combustion Air: Outdoor combustion air is
to be provided through one or two permanent
openings. The minimum dimension of these air
openings is 3 inches (76 mm).
a. Two Permanent Opening Method: Provide
two permanent openings. One opening is to
begin within 12 inches (305 mm) of the top of
the space and the other is to begin within 12
inches (305 mm) of the floor. The openings are
to communicate directly or by ducts with the
outdoors or with spaces that freely communicate
with the outdoors. The size of the openings shall
be determined as follows:
i. Where communicating directly or through
vertical ducts with the outdoors each opening
shall have a minimum free area of 1 in
4000 Btu/hr (22 cm
input rating for all equipment in the space.
See Figure 1.3 for openings directly
communicating with the outdoors or Figure
1.4 for openings connected by ducts to the
outdoors.
Figure 1.3: Air Openings – All Air Directly from
Outdoors
Figure 1.4: Air Openings – All Air from Outdoors
through Vertical Ducts
INSTALLATION AND OPERATING INSTRUCTIONS
2
per
2
per 4000 W) of total
ii. Where communicating with the outdoors
through horizontal ducts, each opening shall
have a minimum free area of 1 in
Btu/hr (22 cm
input for all appliances in the space. See
Figure 1.5.
Figure 1.5: Air Openings – All Air from Outdoors
through Horizontal Ducts
b. One Permanent Opening Method: Provide
one permanent opening beginning within 12
inches (305 mm) of the top of the space. The
opening shall communicate directly with the
outdoors, communicate through a vertical or
horizontal duct, or communicate with a space
that freely communicates with the outdoors. The
opening shall have a minimum free area of 1 in
per 3000 Btu/hr of total rated input for all
appliances in the space and not less than the
sum of the cross-sectional areas of all vent
connectors in the space. The gas-fired equipment
shall have clearances of at least 1 inch (25 mm)
from the sides and back and 6 inches (150 mm)
from the front of the appliance. See Figure 1.6
for this arrangement.
Figure 1.6: Air Openings – All Air from Outdoors
through One Opening
2
per 2000
2
per 2000 W) of total rated
2
5

Advertisement

Table of Contents
loading

Table of Contents