DSP Operation Fault
DSP Communication Lost F32
Alarm message
Speed Low Of Fan_A
Speed Low Of Fan_B
Speed Low Of Fan_C
Zero Power
5.5 Type of system fault and trouble shooting
Table 5.3 Type of system fault and trouble shooting
Alarm Message
AC voltage &
frequency are too
high or too low.
(F00-F03)
System
Bus voltage is too
Faulty Or
high or too low
Failure
(F04-F05)
Type
Bus Voltage
Abnormal
(F06)
Insulation
impedance
Fault(F07)
Installation and Opertion Manual
F24
Table 5.2 Alarm Information
Alarm code Solutions
W00
W01
W02
W03
Trouble Shooting
Solution
(1)Pease check mains voltage whether it is complied with local
safety standard
(2)Please check the AC output line is properly connected. Make
sure its output voltage to see if it is normal.
(3)Disconnect PV input and restart the inverter and check whether
fault still exists.
(4)Contact with your local distributor if the fault still exists.
(1)Please check the setting of input mode.
(2)Disconnect PV input and restart the inverter and check whether
fault still exists.
(3)Contact with your local distributor if the fault still exists.
(1)Please check the setting of input mode.
(2)Please try to restart inverter every few minutes for several times
and check whether fault still exists.
(3)Contact with your local distributor if the fault still exists.
(1)Disconnect PV input and restart the inverter and check whether
fault still exists.
(2)Please measure impedance of PV+/PV- to ground whether is over
than 500KΩ.
(3)Please contact your local distributor if impedance is less than
500KΩ.
DSP communication faulty on
control board.
DSP communication faulty on
control board.
Alarm message for speed low of Fan_
A.
Alarm message for speed low of Fan_
B.
Alarm message for speed low of Fan_
C.
It is only a reminding message to show
DC inputs very low and inverter is
about to shut down.
13