Troubleshooting - Mitsubishi Electric PKFY-P20VAM Technical & Service Manual

Series pkfy wall mounted r407c split-type,heat pump air conditioners
Table of Contents

Advertisement

8

TROUBLESHOOTING

6-1. How to check PKFY-P20VAM,PKFY-P25VAM
Part Name
Room temperature
Disconnect the connector, then measure the resistance using a tester.
thermistor(TH21)
(Sorrounding temperature 10°C~30°C)
Liquid pipe
thermistor(TH22)
Gas pipe
thermistor(TH23)
1Measure the resistance between the terminals using a tester.(Surrounding tempreture 25:.)
Vane motor
3
Blue
Yellow
5
1
Red
Orange Pink
Connect pin No.
4
2
Fan motor
1Measure the resistance between the terminals using a tester.(Surrounding tempreture 20:.)
FAN1
1
White
Red
4
Black
6
2Without disassembling the parts, measure the electrical pressure of the gray wire(Signal line) and
Brown
Gray Yellow
3
2
1
CN33
Linear expansion
Disconnect the connector then measure the resistance valve using a tester.
valve
(Coil temperature 20°C)
CN60
White
1
Yellow
2
Orange
3
LEV
White-Red
Blue
4
Red
5
Brown
6
Normal
'
'
4.3k
~9.6k
Open or short
Normal
1-2
1-3
Red-Pink
Red-Blue
400'
White-Black
Red-Black
brown wire (GND) while the power is on.
!At first, check if the electrical pressure is 12V between the
brown wire(GND) and yellow wire(VCC).
Normal
@Slowly start running the fan. It is normal if while the fan rotate once,
the electrical pressure change from 0V to12V then go back to 0V.
If the electrical pressure stay at around 0V or 10V, it means the fan
Abnormal
motor has the defects.
Normal
(1)-(5)
(2)-(6)
Yellow-Brown
150'
Check points
Abnormal
(Refer to the thermistor)
1-4
1-5
Red-Orange
Red-Yellow
± 7%
Normal
195'
200'
(3)-(5)
(4)-(6)
Orange-Red
Blue-Brown
±10%
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pkfy-p25vamPkfy series