Vertical Vent Tables And Figures - Lennox Hearth Products Adagio ADAGIO-EN Installation Instructions Manual

Direct-vent gas fireplace heaters
Table of Contents

Advertisement

VERTICAL VENT FIGURES/TABLES
Notes:
• Secure Vent™ (rigid vent pipe) is shown
in the Figures; Secure Flex™ (flexible vent
pipe) may also be used.
• It is very important that the horizontal/in-
clined run be maintained in a straight (no
dips) and recommended to be in a slightly
elevated plane, in a direction away from the
fireplace of 1/4" rise per foot (20 mm per
meter) which is ideal, though rise per foot
run ratios that are smaller are acceptable all
the way down to at or near level.
• SV4.5VF (Secure Vent), SF4.5VF (Secure
Flex) firestop/spacer must be used anytime
vent pipe passes through a combustible
floor or ceiling. SV4.5HF (Secure Vent),
SF4.5HF (Secure Flex) firestop/spacer must
be used anytime vent pipe passes through
a combustible wall.
• Two 45 degree elbows may be used in place
of one 90 degree elbow. The same rise to
run ratios, as shown in the venting Figures
for 90 elbows, must be followed if 45 degree
elbows are used.
• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF
VERTICAL RISE EXCEPT WHERE AN ELBOW
IS THE ONLY VERTICAL COMPONENT IN
THE SYSTEM (See Figure 29).
u
Ceiling Firestop /
Spacer (SV4.5VF)
u
When using Secure Flex, use Firestop / Spacer
SF4.5VF
Figure 23
- Top Vent - STRAIGHT
WARNING
Under No Circumstances, May Sepa-
rate Sections of Concentric Flexible
Vent Pipe Be Joined Together.
16
V1
u
W hen using Secure Flex, use Firestop /
Spacer SF4.5VF.
v
W hen using Secure Flex, use Firestop /
Spacer SF4.5HF.
Figure 24
Example: If 20 feet total (H+H
vent run is needed, then 4 feet minimum of
(V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For
every 1 foot of (V) vertical, you are allowed
5 feet of (H+H
40 feet
mum total horizontal run of 20 feet.
(12.2 meters)
Maximum
An elbow is acceptable as 1 foot of verti-
cal rise except where an elbow is the only
vertical component in the system. See
Figure 29.
V 1
Figure 25- Top Vent - THREE ELBOWS
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H
u
Ceiling Firestop /
Spacer (SV4.5VF)
v
Wall Firestop/
Spacer (SV4.5HF)
- Top Vent - TWO 90 DEGREE ELBOWS
) horizontal
1
) horizontal run up to a maxi-
1
u
Ceiling
Firestop / Spacer
(SV4.5VF)
H
H 1
Table A
H Maximum
feet
(meter)
feet
5
(1.524)
5
(1.524)
10
(.048)
15
(4.572)
20
(6.096)
V + V
+ H = 40 feet (12.2 m) Max.
1
H = 20 feet (6.096 meters) Max.
V
Example: If 20 feet of (H) horizontal vent run
is needed, then 4 feet minimum of (V) vertical
vent will be required.
This table shows a 1(V) to 5(H) ratio. For
every 1 foot of (V) vertical, you are allowed 5
feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only vertical
component in the system. See Figure 29.
Table B
V Minimum
H +
H
Maximum
1
feet
(meter)
feet
5
(1.524)
Elbow Only
5
(1.524)
1
10
(.048)
2
15
(4.572)

20
(6.096)
4
H + H
= 20 feet (6.096 m) Max.
1
V + V
+ H + H
= 40 feet (12.192 m) Max.
1
1
v
Wall Firestop/
Spacer (SV4.5HF)
u
W hen using Secure Flex, use
Firestop / Spacer SF4.5VF
V
v
W hen using Secure Flex, use
Firestop / Spacer SF4.5HF
V Minimum
(meter)
Elbow Only
1
(0.05)
2
(0.610)

(0.914)
4
(1.219)
(meter)
(0.05)
(0.610)
(0.914)
(1.219)

Advertisement

Table of Contents
loading

Table of Contents