Location of the termination of venting systems should be installed in accordance with the National Solid Fuel UL
Code 1482, manufacturer's recommendations and/or local codes which are applicable. See requirements below or
refer to installation location, Diagram A, for typical locations.
A. The exit termination of mechanical draft system shall not be less than seven (7) feet above grade when
located adjacent to public walkways.
B. A venting system shall terminate at least three (3) feet above any forced air inlet located within ten (10)
feet.
C. The venting system of other than a direct vent appliance shall terminate at least four (4) feet below, four
(4) feet horizontally from one (1) foot above any door, window or gravity air inlet into the building.
D. The vent termination of a direct vent appliance with an input of 50,000 BTU's per hour or less shall be
located at least nine (9) inches from any opening through which vented gases could enter the building.
With an input over 50,000 BTU's per hour, a twelve (12) inch termination clearance shall be required.
E. The vent termination point shall not be installed closer than three (3) feet from an inside corner of an
L-shaped structure.