Download Print this page

Maintenance; Limited Warranty - Gentex 7109CS Installation Instructions Manual

Photoelectric type commercial & commercial residential smoke alarms for the hearing impaired, ac powered with battery backup, 120vac/9vdc

Advertisement

3. Testing with the Test Knob:
a. Rotate test knob counter-clockwise to TEST 1 position, wait up to 20 seconds
for smoke alarm to sound and visual signal flash. If device does not sound after
20 seconds, return device for service.
b. After successfully testing smoke alarm, return test knob to NORMAL (non-test)
position and wait 20 seconds for the smoke alarm to stop sounding.
c. To test unit for high sensitivity, turn test knob clockwise to TEST 2 position.
Smoke alarm should remain silent. Return knob back to normal position. If the
unit sounds during test, the device's sensitivity has become too high and may
cause false alarms. This could mean the smoke alarm is dirty and should be
cleaned as described in maintenance procedure below. If the smoke alarm
continues to alarm for TEST 2 position following cleaning return it to Gentex for
service.
d. To check for proper smoke entry into smoke alarm's sensing chamber. Gentex
recommends using the Home Safeguard Smoke Detector Spray or CHEKKIT®
SMOKE Detector Tester from SDI. This test should be performed once a year
and should be sprayed from a distance no closer than 12 inches from device.

MAINTENANCE

When smoke alarm has been in operation for a period of time or it was installed
prior to the completion of all building construction, the device can become more sen-
sitive due to dirt build-up in smoke alarm's optic sensing chamber which could cause
nuisance alarms or could cause activation from small amounts of smoke build-up.
If this should occur, following this simple washing procedure will restore your
smoke alarm back to its original condition.
For further information, regarding frequency of cleaning and testing, refer to NFPA
72, NFPA, Batterymarch Park, Quincy, MA 02269.
NOTICE: FAILURE TO FOLLOW FULL CLEANING INSTRUCTIONS COULD
RESULT IN DAMAGE TO THIS SMOKE ALARM. DO NOT REMOVE ALL SMOKE
ALARMS AT THE SAME TIME FOR CLEANING.
1. Rotate smoke alarm counter-clockwise to remove it from its mounting plate.
2. Unplug electrical power cord to smoke alarm and remove battery.
3. Select three (3) standard size wash buckets and fill them each with one gallon of
normal tap water (distilled or de-ionized treated water is recommended as a final
rinse if water is extremely hard in your area).
4. Add 1/8 cup of Ivory dishwashing liquid to first bucket of water, mix thoroughly.
Place one dirty smoke alarm into soap water mixture until it becomes completely
covered or submerged.
NOTICE: IF SMOKE ALARMS ARE EXCEPTIONALLY DIRTY, YOU MAY WISH TO
FIRST WIPE OFF ANY EXCESS DIRT BEFORE WASHING SMOKE ALARM SO AS
NOT TO DIRTY THE WASH WATER TOO QUICKLY.
DO NOT open smoke alarm for cleaning. IF SMOKE ALARM
IS OPENED, PRODUCT WARRANTY BECOMES VOID.
NOTICE: ONLY IVORY DISHWASHING LIQUID IS TO BE USED. OTHER BRANDS
ARE NOT RECOMMENDED AND MAY CAUSE YOUR SMOKE ALARM TO
MALFUNCTION.
For a period of 12 months from the date of purchase, or a maximum of 18 months from the date of manufac-
ture, Gentex warrants to you, the original consumer purchaser, that your Smoke Alarm will be free from defects
in workmanship, materials, and construction under normal use and service. If a defect in workmanship, materi-
als, or construction should cause your Smoke Alarm to become inoperable within the warranty period, Gentex
will repair your Smoke Alarm or furnish you with a new or rebuilt replacement Smoke Alarm without charge to
you except for postage required to return the Smoke Alarm to us. Your repaired or replacement Smoke Alarm
will be returned to you free of charge and it will be covered under this warranty for the balance of the warranty
period.
This warranty is void if our inspection of your Smoke Alarm shows that the damage or failure was caused by
abuse, misuse, abnormal usage, faulty installation, improper maintenance, or repairs other than those performed
by us.
ANY WARRANTIES IMPLIED UNDER ANY STATE LAW, INCLUDING IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, APPLY ONLY FOR THE WARRANTY
PERIOD SPECIFIED ABOVE. PLEASE NOTE THAT SOME STATES DO NOT ALLOW LIMITATIONS ON HOW
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these
materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the
application of such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a
substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.
550-0094-TAC
5. Allow smoke alarm to soak for approximately 10 minutes (longer if extremely dirty).
6. Remove smoke alarm from wash water and transfer directly to one of first rinse
7. Finally, transfer smoke alarm to second and final rinse bucket, repeating method
NOTICE: SMOKE ALARMS ARE TO BE AIR DRIED ONLY. DO NOT PLACE
DEVICE IN OVEN, MICROWAVE OR USE A HOT AIR BLOWER TO ACCELERATE
DRYING TIME. THIS COULD RESULT IN DAMAGE TO YOUR SMOKE ALARM.
IMPORTANT: It is recommended to change wash and rinse water after five (5)
smoke alarms. If your devices are extremely dirty, water should be changed more
frequently.
arise, please contact Gentex Corporation.
yourself. This will void your warranty. See "TO RETURN A SMOKE ALARM" for
instructions to return smoke alarm that does not operate properly. DO NOT
TRY TO FIX IT YOURSELF.
IMPORTANT: Gentex recommends smoke alarm be tested a minimum of once a
week.
may ignite and damage the smoke alarm as well as your home. The test feature
of your smoke alarm accurately simulates smoke conditions and tests the
device's functions as required by ANSI/UL.
smoke alarm. These openings are designed to allow air to pass through your
smoke alarm, thus sampling the air around the device.
unless the combination has been evaluated and found suitable for that
purpose.
NOTICE: FAILURE TO REGULARLY CLEAN SMOKE ALARM WILL RESULT IN
FALSE ALARMS. A BUILD UP OF DUST CREATES AN OBSCURATION THAT
SIMULATES SMOKE. THIS MEANS UNIT WILL GO INTO ALARM WITHOUT A FIRE
CONDITION.
TO RETURN A SMOKE ALARM
1. Rotate unit counter-clockwise to remove from its mounting plate.
2. Unplug electrical power cord or connector to smoke alarm and remove battery. Do
3. Carefully pack (manufacturer is not responsible for damage) and return to
4. Return to: Gentex Corp., 10985 Chicago Dr., Zeeland, MI 49464. Prior to

LIMITED WARRANTY

LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU.
GENTEX WILL NOT BE LIABLE FOR ANY LOSS, DAMAGE, INCIDENTAL OR CONSEQUENTIAL
DAMAGES OF ANY KIND ARISING IN CONNECTION WITH THE SALE, USE, OR REPAIR OF THIS SMOKE
ALARM. PLEASE NOTE THAT SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF
INCIDENTAL OR CONSEQUENTIAL DAMAGES. SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU.
If a defect in workmanship, materials, or construction should cause your Smoke Alarm to become inoperable
within the warranty period, you must return the Smoke Alarm to Gentex postage prepaid. You must also pack
the Smoke Alarm to minimize the risk of it being damaged in transit. You must also enclose a return address.
Smoke Alarms returned for warranty service should be sent to: Gentex Corporation, 10985 Chicago Drive,
Zeeland, MI 49464.
If we receive a Smoke Alarm in a damaged condition as the result of shipping, we will notify you and you
must file a claim with the Shipper.
THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER
RIGHTS WHICH VARY FROM STATE TO STATE.
GENTEX CORPORATION
10985 CHICAGO DRIVE, ZEELAND, MI 49464
PHONE: 1-800-436-8391
www.gentex.com
Agitate for 5 or 10 seconds to flush out any remaining dirt left inside smoke alarm's
housing.
buckets containing clear water. Allow smoke alarm to become completely
submerged, agitate once more for 5 or 10 seconds to remove soap residue.
found in Step 6. Remove unit to a clean dry area for a period of 48 hours to allow
it to thoroughly dry.
In the event you experience difficulty in the cleaning of device(s) or if questions
If smoke alarm does not work properly, do not try and fix it
Never use an open flame of any kind to test your unit. You
Do not cover, tape, or otherwise block the openings of
Smoke alarms are not to be used with detector guards
Should you experience problems with your smoke alarm, proceed as follows:
not ship smoke alarm with battery installed.
manufacturer. Include complete details as to exact nature of difficulties being
experienced and date of installation.
returning, call Gentex at 1-800-436-8391 or e-mail FP_RMA@gentex.com to
obtain RMA Number from return department.
9-1-93
Page 7-6

Advertisement

loading

This manual is also suitable for:

7109ls7139ls7139cs7109csx7139csx