4-11. Positioning Jumper Links

200 VOLTS
3
1

4-12. Electrical Service Guide

Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 1999 National Electrical Code (NEC)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 "Time-Delay" fuses are UL class "RK5" .
3 "Normal Operating" (general purpose − no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and
above).
2
230 VOLTS
153 980−C
1
Circuit Breaker
, Time-Delay
Normal Operating
Return To Table Of Contents
Check input voltage available at
site and listed on the machine rating
label.
1
Jumper Links Access Door
Open door.
2
Jumper Link Label
Check label − only one is on unit.
3
Input Voltage Jumper Links
Move jumper links to match input
voltage.
Close and secure access door.
Tools Needed:
200
32
2
35
3
45
10
89
(27)
10
3/8 in
Ref. 802 476-C
230
28
30
40
10
118
(36)
10
OM-1325 Page 15