Mode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (3 of 3)
Item Field
After the last item, the control returns to the first item in the menu.
16
Range
MINIMUM ON TIME
Select the minimum amount of time that
the stage contact must remain on before it
0:10 to 5:00 min
is allowed to turn off.
Note: This setting is only available when
STAGE MODE is set to P.
MINIMUM OFF TIME
Select the minimum amount of time that
the stage contact must remain off before it
0:10 to 5:00 min
is allowed to turn back on.
Note: This setting is only available when
STAGE MODE is set to P.
PUMP DELAY
OFF, 0:20 to
Select the boiler pump purge time after
9:55 min, On
shutting off the boiler.
WARM WEATHER SHUT DOWN
35 to 100°F
Select the heating system warm weather
(2 to 38°C),
shut down for outdoor reset operation. Heat
OFF
demands are ignored once the outdoor air
temperature exceeds this setting.
TEMPERATURE UNITS
°F or °C
Select to display temperature in degrees
Fahrenheit or in degrees Celsius.
Description
EM-10-40 Operation and Instruction Manual