Default Settings; Adjust Menu - Slant/Fin EM-10 Operation Manual

Electric boiler control
Table of Contents

Advertisement

Mode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (1 of 3)
Enter Adjust Menu
Item
Item Field
Continued on next page.
14
Next Item
Change Value
Item
Range
MODE
1 to 8
Select the operating mode for the control.
STAGE MODE
Select the staging operation to be either
automatic or manual.
PId or P
(PId = automatic)
(P = proportional)
OFF,
BOILER TARGET
70 to 220°F
Select the boiler target temperature while
(21 to 104°C)
a setpoint demand is present.
OUTDOOR START
Select the outdoor starting temperature
35 to 85°F
used in the reset ratio for the heating
(2 to 29°C)
system. Typically set to the desired building
temperature.
OUTDOOR DESIGN
Select the outdoor design temperature used
-60 to 32°F
in the reset ratio for the heating system. Set
(-51 to 0°C)
to the coldest annual outdoor temperature
in the local area.
BOILER START
Select the starting water temperature used
35 to 150°F
in the reset ratio calculation for the heating
(2 to 66°C)
system. Typically set to the desired building
temperature.
BOILER DESIGN
Select the boiler design water temperature
70 to 220°F
used in the reset ratio calculation for the
(21 to 104°C)
heating system. Set to the boiler water
temperature required to heat the building on
the coldest annual outdoor temperature.
BOILER OUTLET MAXIMUM
120 to 225°F
Select the maximum boiler outlet
(49 to 107°C)
temperature. Exceeding this temperature
shuts off the boiler.
The Program menu items are the programmable settings
used to operate the system. Press and hold all three
buttons simultaneously to enter the Program menu
Description
EM-10-40 Operation and Instruction Manual
Access
Setting
Factory
Installer
Default
Setting 4
Factory
Installer
Factory
Installer
Factory
Installer
Factory
Installer
Factory
Installer
Factory
Installer
Factory