Preparing The Install Location; Mounting Bracket; Ductwork; Static Pressure Testing - Accurex XRRS Installation, Operation And Maintenance Manual

Fire ready hood
Table of Contents

Advertisement

Preparing the Install Location

Mounting Bracket - The mounting bracket and hood must be centered over the range. If the range is not in place,
the center marking should be relative to it's final position. Refer to page 7 for bracket mounting points, rear access
holes and access points.
Ductwork - The ductwork and fittings used for outside venting (if applicable) must be carefully selected to ensure
that the static pressure is in line with the fan parameters. The table below displays maximum duct length allowed for
the various fan options.
Hood
NFPA 101
Width
Compliance
No
No
No
No
30 inches
Yes
Yes
Yes
Yes
No
No
No
No
36 inches
Yes
Yes
Yes
Yes
Maximum duct length equals horizontal and vertical duct runs plus duct components such as fittings, elbows, and transitions.
For installations requiring vertical duct venting to an inline fan and NFPA 101 compliance, the hood should be
adapted from a 7-inch round duct access hole to a minimum 12-inch duct.
For installations requiring vertical duct venting to an inline fan and NFPA 101 compliance is NOT required, the hood
can be adapted to a minimum 10-inch duct.
The amount of fittings and ductwork directly affects the resistance or static pressure placed on the system. If the
system is not within the proper static pressure range, the heat sensors and controls will be adversely affected and
will impact the proper function of the safety controls. Therefore it is required that airflow testing be recorded along
with installation documentation. The air testing is accessed by the removal of the grease tray and measured with
an airflow pressure gauge.
Static Pressure Testing - The magnehelic gauge test port opening is located
beneath the grease tray. The static pressure needs to be measured to ensure
airflows meet design criteria. The airflow is measured by attaching the gauge
tubing to the magnehelic gauge inlet, and the hood fitting is attached to the
grease drain hole beneath the grease tray.
A reading of 0.45 to 0.85 inches wg. is required to meet design standards.
This reading will correspond to the static pressure of the ductwork, hood
and fan combination.
Fan Type
Internal
Front (recirculating)
Internal
Rear Discharge
Inline Duct Fan
Exterior Wall Fan
Internal
Front (recirculating)
Internal
Rear Discharge
Inline Duct Fan
Exterior Wall Fan
Internal
Front (recirculating)
Internal
Rear Discharge
Inline Duct Fan
Exterior Wall Fan
Internal
Front (recirculating)
Internal
Rear Discharge
Inline Duct Fan
Exterior Wall Fan
WARNING
CFM
Venting
(at hood)
140
250
Vertical Duct
470
Vertical Duct
150
500
500
Vertical Duct
510
Vertical Duct
550
140
250
Vertical Duct
470
Vertical Duct
150
500
500
Vertical Duct
510
Vertical Duct
550
Duct Length
(maximum)
Not applicable
Not applicable
35 feet
20 feet
Not applicable
Not applicable
35 feet
20 feet
Not applicable
Not applicable
35 feet
20 feet
Not applicable
Not applicable
35 feet
20 feet
Magnehelic Gauge
Magnehelic Gauge
Test Port
Test Port
Fire Ready Hood
5