Recommended Service
and Recertification Schedule
WARNING
Safety glasses must be worn whenever service
operations are performed.
Cleaning
Suppression Nozzles
Fusible Links
Extinguisher Tank
26
Fire Ready Hood
Every
Monthly
Annually
10 years
Yes
Yes
Inspect
Inspect
Inspect
Replace
Inspect
Recertify
Replace

Replacement Parts

Part
Description
Number
Fire Ready Annual Service Kit
479683
(3) Links and Service Tag
Fire Ready Recharge Kit
479684
Tank Assembly fully charged with adapter
Fire Ready Test Kit, Tank Assembly
479685
Nitro only with adapter and test link
Fire Ready Tank Kit, Tank Assembly
479686
Empty with adapter
Fire Ready Test Kit
479687
Set of 2 Test Links, 4 Nozzle Caps and
1 Safety Key
Fire Ready Electrical Disconnect Box
479688
208-240VAC/50A (as replacement)
Fire Ready 3/4-inch Gas Valve
479689
115VAC (as replacement)
479690
Fire Ready 60W Shatterproof Bulb, pack of 2
479691
Fire Ready Fusible Links, 212°F, 3 links
479692
Fire Ready Fusible Links, 280°F, 3 links
479693
Fire Ready Nozzle Caps, set of 10
Fire Ready Wire Rope Assembly Set
479694
Hood Width of 30 inches
Fire Ready Wire Rope Assembly Set
479695
Hood Width of 36 inches
Fire Ready Replacement Charcoal Filters
479696
"F" Calibrations, pack of 10
479697
Fire Ready Grease Entrapment Filter
479698
Fire Ready Grease Filter Cup
Fire Ready Replacement Fuse Kit for Control
479699
Systems