Thermostat wiring for gas unit heaters hd/hdb, hds/hdc, pts/bts, ptc, pdp/bdp, and duct furnaces “d”, “h”, “i”, & “o” series
Hide thumbs Also See for TH5220D1003:

Advertisement

Thermostat Function Program Selection
To enter thermostat setup mode, press and hold the s and
FAN buttons until the display changes to setup mode. Use
the s and t buttons to change settings, the NEXT button
to advance to the next setting, and the DONE button to save
the settings and exit from the setup mode.
For gas fired unit heaters and duct furnaces (non-factory
supplied blower) with model numbers shown on the opposite
side, refer to Table 2.1 typical thermostat function settings.
For all other system units (factory supplied blower), refer to
the job specific unit wiring diagram provided with the unit.
For deviations to these wiring diagrams or the job specific
wiring diagrams, consult the factory.
For additional information, refer to the vendor literature
supplied with the thermostat.
Table 2.1 - Typical Thermostat Function Program Settings ➀
Function
Number
1
3
5
Heat cycle rate (CPH)
6
Second stage heat cycle rate (CPH)
9-12
Cooling functions
14
Temperature display
15-26
Cooling and emergency heat functions
27
Heat temperature range stops
28
Cool temperature range stops
➀ See Honeywell instructions that shipped with stat for more information and additional setting options.
Commercial Products Group • Modine Manufacturing Company • 1500 DeKoven Avenue • Racine, Wisconsin 53403-2552
"D" & "H" Model Series and Gas Fired Unit Heaters - Phone: 1.800.828.4328 (HEAT) • Fax: 1.800.204.6011
"I" & "O" Model Series - Phone: 1.866.823.1631 (Toll Free) • Fax: 1.800.204.6011
© Modine Manufacturing Company 2009
Feature
System type
Fan control
Figure 2.1 - Buttons to Press to Enter Function

Programming Mode

Press and hold to enter
function programming mode
Typical
Setting
3
Single stage heat only with fan
6
2 heat/2 cool conventional (cooling by others)
7
2 heat/1 cool conventional (cooling by others)
0
Gas or oil furnace — equipment controls fan in heating
5
For gas or oil furnaces of less than 90% efficiency
3
For furnaces of over 90% efficiency
5
For gas or oil furnaces of less than 90% efficiency
3
For furnaces of over 90% efficiency
0
1
90
Default value, can be set 40-90 in increments of 1°F
80
For PTC models, this setting must be changed to 80
50
6-436.9
Description
Fahrenheit
Celcius
Litho in USA