Samsung ASV18PULNXEA Service Manual page 86

Split-type indoor unit outdoor unit
Table of Contents

Advertisement

Comp Vlimit error/Comp current limit error
Indoor display
Outdoor display
1.Checklist :
1) Is the IPM Shunt(A*V18***:R451,R452,R453,A*V24***:R413,R414,R415) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
Is the O.C error occurred?
YES
Is the connection of compressor
wire is normal?
YES
Is the O.C error occurred again?
YES
Is the condition of indoor/outdoor
temperature normal load?
YES
Is the position of temperature
sensor and sensing value normal?
YES
Is the compressor body and
interphase resistance insulated?
NO
Exchange the compressor
Outdoor error
Comp Vlimit error/Comp current limit
error
NO
NO
NO
NO
YES
NO
YES
Terminate the service
Connect the comp wire normally
Terminate the service
Restart after returning to the normal load
NO
Is the O.C error
Terminate the
occurred again?
service
Correct the sensor position or exchange the sensor
Exchange the Outdoor PBA
12-21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents