Xinje VB3 User Manual page 47

Frequency inverter
Hide thumbs Also See for VB3:
Table of Contents

Advertisement

tion
P3.04
AVR function
P3.05
Slip frequency compen-
sation
P3.06
Jog frequency
P3.07
Accelerate time of jog
P3.08
Decelerate time of jog
P3.09
Communication
configuration
P3.10
Inverter address
Communication timeout
P3.11
detect time
P3.12
Inverter answer delay
P3.13
Proportion of communi-
cation frequency
P3.14
Accerlate time 2
P3.15
Decerlate time 2
P3.16
Accerlate time 3
P3.17
Decerlate time 3
P3.18
Accerlate time 4
P3.19
Decerlate time 4
P3.20
Accerlate time 5
P3.21
Decerlate time 5
P3.22
Accerlate time 6
P3.23
Decerlate time 6
P3.24
Accerlate time 7
1: Enabled
0: disabled
1: enable all the time
2: Disabled when decelerating
0~150%
0.10~50.00Hz
0.1~60.0s
0.1~60.0s
LED lowest bit: baud rate
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
LED ten bit: data format
0: 1-7-2 foramt, no parity
1: 1-7-1 format, Odd
2: 1-7-1 format, Even
3: 1-8-2 format, None
4: 1-8-1 format, Odd
5: 1-8-1 format, Even
6: 1-8-1 format, None
(When use Modbus-RTU communica-
tion mode, please select data mode
3~6)
LED hundred bit: undefined
0~248
0: broadcast address
248: inverter as the host address
(function is developing)
0.0~1000.0s
0.0: Detection disabled
0~1000ms
0.01~1.00
0.1~6000.0
0.1~6000.0
0.1~6000.0
0.1~6000.0
0.1~6000.0
0.1~6000.0
0.1~6000.0
0.1~6000.0
0.1~6000.0
0.1~6000.0
0.1~6000.0
V5 series inverter
1
0
1%
0%
0.01Hz
5.00Hz
0.1s
5.0s
0.1s
5.0s
1
054
1
1
0.1s
0.0s
1
5ms
0.01
1.00
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
0.1
10.0
×
×
×
×
×
×
×
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vb5V5

Table of Contents