ELX SERIES VENTILATOR MODEL DESCRIPTION MODEL “ELX-BBC” MODEL “ELX-BB” MODEL “ELX” APPLICATION - Wall mounted APPLICATION - Used for cafeteria lines or APPLICATION - Used for typical island canopy style. any other single line island arrangement. style back to back cooking arrangement.
Page 5
Gaylord Ventilator model numbers are made up of an alphabetic prefix followed by a series of alphabetic and/or numeric suffixes to designate the style of the ventilator and various options. Sequence of model numbers is as follows. 1.______ 2.______ 3._______ 4._______...
Page 6
Series hood may be equipped with a fan, auto start controller, and/or light switch mounted on the face of the hood. GREASE EXTRACTION The Gaylord Industries Patent Pending “XGS” Extractor and IMC Cartridge is designed to deliver the absolute optimum UL 710 Recognized XGS...
A maintenance rotation should be initiated at the point of start up by a Gaylord Industries certified Service Agent to address any maintenance, or repair issues that may be required.
Factor y trained ser vice agencies are cer tified by Gaylord Industries to perform these inspections. For the name and phone num- ber of your nearest agent, call 1-800-547-9696 or go online to visit our...
Page 9
UV PREVENTATIVE MAINTENANCE CERTIFIED SERVICE AGENT MAINTENANCE WARNING! Warning: Do NOT defeat any interlocks during cleaning and maintenance! Replacing UV Lamps system inspection schedule described in NFPA-96 and on the previous Danger! page in this tech manual. These tasks involve potential exposure to high doses of UV light and live electrical components.
Page 10
UV PREVENTATIVE MAINTENANCE CONTINUED CERTIFIED SERVICE AGENT MAINTENANCE WARNING! Warning: Do NOT defeat any interlocks during cleaning and maintenance! 11. Check all wires for damage • Replace any wires showing damage 12. Lubricate each of the new UV lamp(s) before installing with a small amount of G-510 or similar detergent 13.
Page 11
OPTIONAL FIRE / BALANCING DAMPER GBD SERIES Gaylord System Balancing (GBD) The ELX Series Ventilator will optionally come with a Gaylord Industries Listed balancing damper. The options available are the GBD-IS (balancing only damper), GEBD (electrical balancing dam- per), and the GFBD (fire balancing damper). The GBD-IS is set from below and performs the task of raising or lowering the exhaust airflow to any section that it is installed on.
Page 14
UV BALLAST BOX WIRING The UV Hood Wiring Board is an integral part of the UV interlock sure to remove it immediately after the repair has been completed. system. All interlock activations are indicated by the LED’s next to Pressure switches can be adjusted by removing the clear cover. each component’s wire attachment.
Start-up report. Once installed, connect the internal UV plug to the Module. • Send a copy of the Start-up report to Gaylord and keep a Make sure to turn the connector until it stops. copy for your records.
Measuring Airflow (Multiple Section) Measuring Airflow (Single Section) During the course of the start up the Gaylord Industries representative The ELX hood has been designed to give you an approximate air- or balancer will have to balance all hoods common to a single fan flow per linear foot of hood based on the static pressure measured simultaneously.
Page 17
1.60 doors, or cross drafts in the vicinity of the hood’s should be noted, and lastly, all observations, and values need to be recorded and pro- vided to Gaylord Industries for safe keeping. 1.40 SP adder (1500 FPM) SP adder (1800 FPM) 1.20...
TROUBLESHOOTING SYMPTOM POSSIBLE PROBLEM CORRECTIVE ACTION SMOKE LOSS Smoke Loss - Hood is not exhausting Broken or slipping belt on the exhaust properly. hoods static tap. Static values should fan. be in accordance with Figure 21. Confirm proper rotation of the exhaust fan.
Page 19
TROUBLESHOOTING SYMPTOM POSSIBLE PROBLEM CORRECTIVE ACTION EXHAUST FAN If the fan switch is turned on to the Overload protector on the magnetic Push the “Reset” button on the exhaust position but the exhaust fan starter tripped. magnetic starter and turn the fan does not come on.
Page 20
TROUBLESHOOTING UV SYSTEM Danger! of injury to skin and eyes and in the case of electrical shock, injury or death! For a list of CSA’s go to http://www.gaylordusa.com and exposure to UV light and live electrical components. There is a risk go to Service for a list of companies nearest you.
Page 21
Ballast box. Access cover insulation is missing Remove old insulation. Replace with or has broken down approved insulation. Contact Gaylord for details. • CUV-1000 not functioning as intended See CUV-1000 Controller Technical Manual...
Page 22
TROUBLESHOOTING UV STATUS LIGHTS UV Status Lights Green Yellow UV System Mode “UV System On” “UV Lamp Failure” “UV Safety Interlock Activated” Light on Light on Light on All UV Lamps ON “Normal” One or more UV Lamps not working UV Module un-plugged No Power to the UV Module (All doors closed) UV Access door Open...
Page 24
PARTS LIST GAYLORD PART NUMBER DESCRIPTION ILLUSTRATION 19176 Damper Control Motor (24 Volt) For GFBD/GEBD Model Dampers 20129 UV Hood Wiring Board (120 / 240 VAC) 30529 UV Contactor 11399 Relay 11413 Base SPDT 19726 UV Status Lamp - Green...
NFPA or IFC codes and standards. Caution: Fire extinguishing system piping installed on the hood at job site should be coordinated with the Gaylord Manufacturer to ensure SWITCH piping does not interfere with hood’s operation/performance. Improper installation may void Listings of the hood.
For “ELX” Series Ventilators May 2010 The Gaylord “ELX ” Series hood and component parts furnished with the hood by Gaylord Industries or the Licensed Gaylord Manufacturer are warranted by Gaylord Industries or the Licensed Gaylord Manufacturer producing ventilator to be free from defects of material and workmanship under normal use when installed, operated and serviced in accordance with factory recommendations.