  • Page 1: Technical Data

    EEDEN07-721 technical data ERHQ011-016AA EKHBH007AC / EKHBX007AC EKSWW150-300...
  • Page 2 Altherma ERHQ011-016AA EKHBH007AC / EKHBX007AC EKSWW150-300 Daikin’s unique position as a man- “The present publication is drawn up by way of information only and ISO14001 assures an effective environmental ufacturer of air conditioning equip- does not constitute an offer binding upon Daikin Europe N.V.. Daikin...
  • Page 3 EEDEN07-721 technical data ERHQ011-016AA EKHBH007AC / EKHBX007AC EKSWW150-300...
  • Page 4: Heat Pump

    • Chillers • R-410A • ALTHERMA l l e h e r h e r 1 0 A A l t A l t R - 4 C h i Heating only Heat pump • Altherma • Chillers...
  • Page 5: Table Of Contents

    ......... . . 15 • Altherma • Outdoor units...
  • Page 6: Features

    A l t E R H R - 4 • Cost effective alternative to a fossil fuel boiler • Easy to install • Low energy bills and low CO2 emissions • Total solution for year round comfort • Altherma • Outdoor units...
  • Page 7: Specifications

    0.98 0.98 0.98 0.98 0.98 0.98 Area Nr of Stages Tube type Hi-XSS(8) Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller Quantity Air Flow Rate Heating High m³/min (nominal at Cooling High m³/min 230V) • Altherma • Outdoor units...
  • Page 8 Pressure Cooling Sound Power Sound Pressure Sound Level Heating Sound (Night quiet) Pressure Cooling Sound Pressure Refrigerant Type R-410A Charge Control Expansion valve (electronic type) Nr of Circuits Refrigerant Oil Type Daphne FVC68D Charged Volume • Altherma • Outdoor units...
  • Page 9: Electrical Specifications

    27.4 31.9 running Current Recomended fuses Wiring For Power Remark See installation manual outdoor unit 4PW37976-1B connections Supply For connection Remark See installation manual outdoor unit 4PW37976-1B with indoor Power Supply Intake Outdoor unit only • Altherma • Outdoor units...
  • Page 10: Capacity Tables

    Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range D1= 3-8°C 3. Power input Power input is total input of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006 Pump power input to be added=90W (according EN14511) 3TW57752-1 • Altherma • Outdoor units...
  • Page 11: Heating Capacity Tables

    Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range D1= 3-8°C 3. Power input Power input is total input of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006 Pump power input to be added=90W (according EN14511) 3TW57752-1 • Altherma • Outdoor units...
  • Page 12: Dimensional Drawing & Centre Of Gravity

    Liquid pipe connection ∅9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole ∅34) control wiring intake (knock out hole ∅27) Drain outlet 3TW57764-1 • Altherma • Outdoor units...
  • Page 13: Piping Diagram

    Port Compressor 5/16’ Field Piping ø15.9 C 1220T-0 Accumulator Outdoor Unit Indoor Unit Heating Cooling Stop Valve (With Service Port 5/16’ Flare) Screw Conn. Check Valve Flare Conn. Flange Conn. Pinched Pipe Spinned Pipe 3TW57765-1 • Altherma • Outdoor units...
  • Page 14: Wiring Diagram

    • Outdoor units • R-410A • ERHQ Wiring diagram 6 - 1 External connection diagram ELECTRICAL CONNECTION DIAGRAM ALTHERMA (011/014/016 CLASS) Standard parts Power supply Applicable for the following models: OUTDOOR UNIT OUTDOOR UNIT: ERHQ011/014/016AAV3 3 core unit power supply: 230V + earth...
  • Page 15: Sound Data

    = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa. If sound is measured under actual installation conditions, the measured value Measuring location will be higher due to environmental noise and sound reflections. (Discharge side) • Altherma • Outdoor units...
  • Page 16 = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa. If sound is measured under actual installation conditions, the measured value Measuring location will be higher due to environmental noise and sound reflections. (Discharge side) • Altherma • Outdoor units...
  • Page 17 ..........39 • Altherma • Indoor units...
  • Page 18: Features

    A l t E K H R - 4 • Cost effective alternative to a fossil fuel boiler • Easy to install • Low energy bills and low CO2 emissions • Total solution for year round comfort • Altherma • Indoor units...
  • Page 19: Specifications

    Liquid side diameter 6,35 6,35 6,35 9,52 9,52 9,52 Sound Level Sound Pressure Operation Ambient Heating °C -20~35 -20~35 -20~35 range Waterside Heating °C 25 - 55 25 - 55 25 - 55 15~55 15~55 15~55 • Altherma • Indoor units...
  • Page 20: Electrical Specifications

    Select diameter and type according to national and local heater regulations Electric heater Type Power Supply Phase Frequency Hz Voltage Current Running 15.1 15.1 15.1 Current Voltage range Minimum -10% -10% -10% Maximum +10% +10% +10% • Altherma • Indoor units...
  • Page 21 Select diameter and type according to national and local heater regulations Electric heater Type Power Supply Phase Frequency Hz Voltage Current Running 22.6 22.6 22.6 Current Voltage range Minimum -10% -10% -10% Maximum +10% +10% +10% • Altherma • Indoor units...
  • Page 22 3V3 model which has only 1 capacity step. For 6W1 and 9W1 models, neutral line only required for optional booster heater power supply. Model without optional back up heater is powered via outdoor unit. • Altherma • Indoor units...
  • Page 23: Options

    • Indoor units • R-410A • EKHBH Options • Altherma • Indoor units...
  • Page 24 EKSWWU200V3 Sanitary warm water tank 200l 2~230V 0(*) 0(*) 0(*) 0(*) EKSWWU300V3 Sanitary warm water tank 300l 2~230V 0(*) 0(*) 0(*) 0(*) EKHBDP Option kit for condensate free cooling operation *if neutral line is available 3TW57759-2A • Altherma • Indoor units...
  • Page 25: Dimensional Drawing & Centre Of Gravity

    Suction pipe connection ∅15.9 flare connection Liquid pipe connection ∅9.52 flare connection Shut off valves with drain/fill valve (accessory delivered with unit) Holes for fixation Switchbox terminals Switchbox terminals option sanitary warm water tank Wallbracket 3TW57754-1 • Altherma • Indoor units...
  • Page 26: Piping Diagram

    Heating (EKHBX + EKHBH) Inlet water Thermistor Refrigerant Liquid Side Thermistor Check Valve Flare Conn. Screw Conn. Flange Conn. Pinched Pipe Spinned Pipe Outlet Water Backup heater Thermistor Outlet Water Heat-exchanger Thermistor Thermistor Description 3TW57755-1 • Altherma • Indoor units...
  • Page 27: Wiring Diagram

    6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow Wire colour Field wiring BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 3TW57556-4 7 For EKSWWU*V3, refer to option manual • Altherma • Indoor units...
  • Page 28 6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow Field wiring Wire colour BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 3TW57556-5 7 For EKSWWU*V3, refer to option manual • Altherma • Indoor units...
  • Page 29 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor unit, outdoor unit and EKSWW option. Do not operate the unit by short-circuiting any protection device. For EKSWWU*V3, refer to option manual. • Altherma • Indoor units...
  • Page 30 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor unit, outdoor unit and EKSWW option. Do not operate the unit by short-circuiting any protection device. For EKSWWU*V3, refer to option manual. • Altherma • Indoor units...
  • Page 31 6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow Field wiring Wire colour BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 3TW57556-2 7 For EKSWWU*V3, refer to option manual • Altherma • Indoor units...
  • Page 32 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor unit, outdoor unit and EKSWW option. Do not operate the unit by short-circuiting any protection device. For EKSWWU*V3, refer to option manual. • Altherma • Indoor units...
  • Page 33 6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow See note 7 Field wiring For EKSWWU*V3 Option BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 3TW56716-3C 7 For EKSWWU*V3, refer to option manual • Altherma • Indoor units...
  • Page 34 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor unit, outdoor unit and EKSWW option. Do not operate the unit by short-circuiting any protection device. For EKSWWU*V3, refer to option manual. • Altherma • Indoor units...
  • Page 35: External Connection Diagram

    Signal Indoor unit Thermistor cable Note: min. distance to power cable = 3cm User interface 3TW56719-6A ELECTRICAL CONNECTION DIAGRAM ALTHERMA (011/014/016 CLASS) Standard parts Power supply Applicable for the following models: OUTDOOR UNIT OUTDOOR UNIT: ERHQ011/014/016AAV3 3 core unit power supply: 230V + earth...
  • Page 36: Installation

    If leaving water temperature is below 12°C, condensation on water piping will happen. Dry bulb temperature [°C] 1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDP - drainpan kit must be considered. 4TW57759-3 • Altherma • Indoor units...
  • Page 37: Operation Range

    : Units with optional back up heater Leaving condenser water temperature (°C) Outdoor temp. (°CDB) : Booster heater operation only : Units with optional back up heater or booster heater operation only Water temperature sanitary tank (°C) 4TW57553-1A • Altherma • Indoor units...
  • Page 38 • Indoor units • R-410A • EKHBH Operation range ERHQ - EKHBH(X)016 COOLING MODE HEATING MODE outdoor temp (°CDB) outdoor temp (°CDB) leaving condensor leaving evaporator water temperature (°C) water temperature (°C) NO HEAT PUMP OPERATION BACK UP HEATER ONLY 4TW57753-1A • Altherma • Indoor units...
  • Page 39: Hydraulic Performance

    ESP: External static pressure Flow: waterflow trough the unit Warning: Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrate in the technical specifications. 4TW56749-2 • Altherma • Indoor units...
  • Page 40 See also minimum and maximum allowed ESP: external static pressure water flowrange in the technical specifications. Flow: waterflow through the unit 2. Water quality must be according to EN directive EC 98/83 EC. 4TW57759-1 • Altherma • Indoor units...
  • Page 41 ..........63 • Altherma • Indoor units...
  • Page 42: Features

    A l t E K H R - 4 • Cost effective alternative to a fossil fuel boiler • Easy to install • Low energy bills and low CO2 emissions • Total solution for year round comfort • Altherma • Indoor units...
  • Page 43: Specifications

    Manometer Drain valve / Fill valve Shut off valve Air purge valve Total water volume (6) Refrigerant Gas side diameter 15,9 Circuit Liquid side diameter 6,35 6,35 6,35 9,52 9,52 9,52 Sound Level Sound Pressure • Altherma • Indoor units...
  • Page 44: Electrical Specifications

    Current Running Current Voltage range Minimum -10% -10% Maximum +10% +10% +10% Wiring For power Quantity of wires connections supply backup Type of wires Select diameter and type according to national and local heater regulations • Altherma • Indoor units...
  • Page 45 Type of wires Select diameter and type according to national and local heater regulations Electric heater Type Power Supply Phase Frequency Voltage Current Running 22.6 22.6 22.6 Current Voltage range Minimum -10% -10% Maximum +10% +10% +10% • Altherma • Indoor units...
  • Page 46 3V3 model which has only 1 capacity step. For 6W1 and 9W1 models, neutral line only required for optional booster heater power supply. Model without optional back up heater is powered via outdoor unit. • Altherma • Indoor units...
  • Page 47: Options

    • Indoor units • R-410A • EKHBX Options • Altherma • Indoor units...
  • Page 48 EKSWWU200V3 Sanitary warm water tank 200l 2~230V 0(*) 0(*) 0(*) 0(*) EKSWWU300V3 Sanitary warm water tank 300l 2~230V 0(*) 0(*) 0(*) 0(*) EKHBDP Option kit for condensate free cooling operation *if neutral line is available 3TW57759-2A • Altherma • Indoor units...
  • Page 49: Dimensional Drawing & Centre Of Gravity

    Suction pipe connection ∅15.9 flare connection Liquid pipe connection ∅9.52 flare connection Shut off valves with drain/fill valve (accessory delivered with unit) Holes for fixation Switchbox terminals Switchbox terminals option sanitary warm water tank Wallbracket 3TW57754-2 • Altherma • Indoor units...
  • Page 50: Piping Diagram

    Heating (EKHBX + EKHBH) Inlet water Thermistor Refrigerant Liquid Side Thermistor Check Valve Flare Conn. Screw Conn. Flange Conn. Pinched Pipe Spinned Pipe Outlet Water Backup heater Thermistor Outlet Water Heat-exchanger Thermistor Thermistor Description 3TW57755-1 • Altherma • Indoor units...
  • Page 51: Wiring Diagram

    6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow Wire colour Field wiring BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 3TW57556-4 7 For EKSWWU*V3, refer to option manual • Altherma • Indoor units...
  • Page 52 6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow Field wiring Wire colour BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 3TW57556-5 7 For EKSWWU*V3, refer to option manual • Altherma • Indoor units...
  • Page 53 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor unit, outdoor unit and EKSWW option. Do not operate the unit by short-circuiting any protection device. For EKSWWU*V3, refer to option manual. • Altherma • Indoor units...
  • Page 54 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor unit, outdoor unit and EKSWW option. Do not operate the unit by short-circuiting any protection device. For EKSWWU*V3, refer to option manual. • Altherma • Indoor units...
  • Page 55 6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow Field wiring Wire colour BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 3TW57556-2 7 For EKSWWU*V3, refer to option manual • Altherma • Indoor units...
  • Page 56 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor unit, outdoor unit and EKSWW option. Do not operate the unit by short-circuiting any protection device. For EKSWWU*V3, refer to option manual. • Altherma • Indoor units...
  • Page 57 6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow See note 7 Field wiring For EKSWWU*V3 Option BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet 3TW56716-3C 7 For EKSWWU*V3, refer to option manual • Altherma • Indoor units...
  • Page 58 This wiring diagram only applies to the indoor unit. Use one and same dedicated power supply for indoor unit, outdoor unit and EKSWW option. Do not operate the unit by short-circuiting any protection device. For EKSWWU*V3, refer to option manual. • Altherma • Indoor units...
  • Page 59: External Connection Diagram

    Signal Indoor unit Thermistor cable Note: min. distance to power cable = 3cm User interface 3TW56719-6A ELECTRICAL CONNECTION DIAGRAM ALTHERMA (011/014/016 CLASS) Standard parts Power supply Applicable for the following models: OUTDOOR UNIT OUTDOOR UNIT: ERHQ011/014/016AAV3 3 core unit power supply: 230V + earth...
  • Page 60: Installation

    If leaving water temperature is below 12°C, condensation on water piping will happen. Dry bulb temperature [°C] 1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDP - drainpan kit must be considered. 4TW57759-3 • Altherma • Indoor units...
  • Page 61: Operation Range

    : Units with optional back up heater Leaving condenser water temperature (°C) Outdoor temp. (°CDB) : Booster heater operation only : Units with optional back up heater or booster heater operation only Water temperature sanitary tank (°C) 4TW57553-1A • Altherma • Indoor units...
  • Page 62 • Indoor units • R-410A • EKHBX Operation range ERHQ - EKHBH(X)016 COOLING MODE HEATING MODE outdoor temp (°CDB) outdoor temp (°CDB) leaving condensor leaving evaporator water temperature (°C) water temperature (°C) NO HEAT PUMP OPERATION BACK UP HEATER ONLY 4TW57753-1A • Altherma • Indoor units...
  • Page 63: Hydraulic Performance

    ESP: External static pressure Flow: waterflow trough the unit Warning: Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrate in the technical specifications. 4TW56749-2 • Altherma • Indoor units...
  • Page 64 See also minimum and maximum allowed ESP: external static pressure water flowrange in the technical specifications. Flow: waterflow through the unit 2. Water quality must be according to EN directive EC 98/83 EC. 4TW57759-1 • Altherma • Indoor units...
  • Page 65 ........71 • Altherma • Sanitary Hot Water...
  • Page 66: Features

    E K S R - 4 • Cost effective alternative to a fossil fuel boiler • Easy to install • Low energy bills and low CO2 emissions • Total solution for year round comfort • Altherma • Sanitary Hot Water...
  • Page 67: Specifications

    3/4’’ FBSP Hot water out Diameter inch 3/4’’ FBSP 2-2 ELECTRICAL SPECIFICATIONS EKSWW150V3 EKSWW200V3 EKSWW300V3 EKSWW200Z2 EKSWW300Z2 EKSWWU150V3 EKSWWU200V3 EKSWWU300V3 Unit Power Supply Phase Frequency Hz Voltage Nominal running current Fuse Size Phase • Altherma • Sanitary Hot Water...
  • Page 68: Options

    • Sanitary Hot Water • R-410A • EKSWW Options EKSWW Kit availibility for EKSWW* Reference Description EKSWW... 150V3/Z2 200V3/Z2 300V3/Z2 EKSWWU... 150V3 200V3 300V3 EKUSWW Option kit for UK EKSWWU150~300V3 EKWBSWW150 Wall bracket for EKSWW150V3 3TW57759-2A • Altherma • Sanitary Hot Water...
  • Page 69: Capacity Tables

    (3) Efficiency of sanitary hot water production: In the ALTHERMA by Daikin system both the heat-pump and the electric booster heater supply the energy to produce sanitary hot water. The higher the portion of energy supplied by the heat-pump, the more energy efficient the system is.
  • Page 70: Dimensional Drawing & Centre Of Gravity

    Water mains out female 3/4’’ BSP Thermistor connection female 1/2’’ BSP Flow (from hydrobox) female 3/4’’ BSP Return (to hydrobox) female 3/4’’ BSP Switchbox Clixon Connection female 3/4’’ BSP Power entrance Required service space around the tank 3TW56714-4A • Altherma • Sanitary Hot Water...
  • Page 71: Wiring Diagram

    • Sanitary Hot Water • R-410A • EKSWW Wiring diagram 6 - 1 External connection diagram ELECTRICAL CONNECTION DIAGRAM ALTHERMA (011/014/016 CLASS) Standard parts Power supply Applicable for the following models: OUTDOOR UNIT OUTDOOR UNIT: ERHQ011/014/016AAV3 3 core unit power supply: 230V + earth...