EEDE06-9
technical data
ERYQ005-007A
EKHBH007A / EKHBX007A
EKSWW150-300

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ERYQ005-007A and is the answer not in the manual?

Questions and answers

Summary of Contents for Altherma ERYQ005-007A

  • Page 1 EEDE06-9 technical data ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300...
  • Page 2 Altherma ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300 ISO14001 assures an effective environmental Daikin units comply with the European “ The present publication is drawn up by way of information only and does not constitute an offer binding management system in order to help protect regulations that guarantee the safety of the upon Daikin Europe N.V..
  • Page 3 EEDE06-9 technical data ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300...
  • Page 4: Cooling Only

    • Chillers • R-410A • ALTHERMA l l e h e r h e r 1 0 A A l t A l t R - 4 C h i Cooling only Heating only Heat pump • Altherma • Chillers...
  • Page 5: Table Of Contents

    ........... 18 • Altherma • Outdoor units...
  • Page 6: Features

    A l t E R Y R - 4 • Cost effective alternative to a fossil fuel boiler • Easy to install • Low energy bills and low CO2 emissions • Total solution for year round comfort • Altherma • Outdoor units...
  • Page 7: Specifications

    Nr of Rows Fin Pitch Nr of Stages Tube type Hi-Xa(8) Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller Quantity Motor Quantity Output Compressor Quantity Motor Model 2YC63BXD#C Type Hermetically sealed swing compressor Motor 1920 Output • Altherma • Outdoor units...
  • Page 8 Maximum m height difference Max. internunit level difference Defrost Method Reverse cycle Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method Inverter controlled Standard Item Installation manual Accessories Quantity Item Drain plug Quantity • Altherma • Outdoor units...
  • Page 9: Electrical Specifications

    1˜ Frequency Voltage 220-440 Voltage range Maximum V +10% Current Maximum Cooling running Heating Current Cooling 16.25 Heating Recomended fuses Wiring For Power Quantity connections Supply For connection Quantity with indoor Remark Included earth wiring • Altherma • Outdoor units...
  • Page 10: Capacity Tables

    Dt = 3∼8°C : Leaving Water Evaporator temperature (°C) Power input : Leaving Water Condensor temperature (°C) Power input is total input according to Eurovent rating standard 6/C/003-2006 Tamb : Ambient temperature (°C) RH=85% • Altherma • Outdoor units...
  • Page 11: Dimensional Drawing & Centre Of Gravity

    Outdoor air thermistor 4 x holes for anchor bolts (M8 or M10) Terminal strip with earth Brand name label Wiring inlet terminal Liquid stop valve (J6.4 CuT) Gas stop valve Service port (J15.9 CuT) 3D051658B • Altherma • Outdoor units...
  • Page 12: Centre Of Gravity

    • Outdoor units • R-410A • ERYQ Dimensional drawing & centre of gravity 4 - 2 Centre of gravity ERYQ The position of foundation bolt 4D042258G • Altherma • Outdoor units...
  • Page 13: Piping Diagram

    Motor operated Propeller fan valve Filter Four way valve on : heating Muffler with filter Field piping Muffler Liquid stop valve Muffler Field piping Discharge pipe Gas stop valve with thermistor Accumulator service port Compressor 3D052750A • Altherma • Outdoor units...
  • Page 14: Wiring Diagram

    AC1, AC2 : Neutral U, V, W, X11A, X12A : Forced operation on/off switch SW (SW1) E1, E2 : Local setting SW (SW4) HR1, HR2 : Connector : Compressor motor 3D052296B : Fan motor : Reactor • Altherma • Outdoor units...
  • Page 15: External Connection Diagram

    NC valve: 3 way valve 2 core 2 core M3S (when EKSWW is installed) R5T - Thermistor water selection sanitary-floorheating temperature Signal Indoor unit Thermistor cable Note: min. distance to power cable = User interface 3TW56719-6 • Altherma • Outdoor units...
  • Page 16: Sound Data

    4 If sound is measured under actual installation conditions, the measured value will be higher due to conditions, the measured value will be higher due to environmental noise and sound reflections. environmental noise and sound reflections. Location of microphone Location of microphone • Altherma • Outdoor units...
  • Page 17 4 If sound is measured under actual installation conditions, the measured value will be higher due to conditions, the measured value will be higher due to environmental noise and sound reflections. environmental noise and sound reflections. Location of microphone Location of microphone • Altherma • Outdoor units...
  • Page 18: Operation Range

    • Outdoor units • R-410A • ERYQ Operation range Outdoor temp. (°CDB) Leaving evaporator water temperature (°C) Outdoor temp. (°CDB) Leaving condenser water temperature (°C) Outdoor temp. (°CDB) : Booster heater operation only Leaving condenser water temperature (°C) 4TW56713-1A • Altherma • Outdoor units...
  • Page 19 ..........30 • Altherma • Indoor units...
  • Page 20: Features

    I n d A l t R - 4 • Cost effective alternative to a fossil fuel boiler • Easy to install • Low energy bills and low CO2 emissions • Total solution for year round comfort • Altherma • Indoor units...
  • Page 21: Specifications

    Max. water pressure pressure Water filter Diameter perfo- rations Material Brass Water circuit Piping connections inch 1"MBSP diameter Piping inch 1"MBSP Safety valve Manometer Drain valve / Fill valve Shut off valve Air purge valve • Altherma • Indoor units...
  • Page 22 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment. ERYQ = 6.35 mm EKHB = 9.52 mm (flare connection) • Altherma • Indoor units...
  • Page 23: Electrical Specifications

    Running Current Electric Type heater Power Supply Phase Frequency Voltage Current Running Current Electric Type heater Power Supply Phase Frequency Voltage Current Running Current Electric Type heater Power Supply Phase Frequency Voltage Current Running Current • Altherma • Indoor units...
  • Page 24: Options

    • Indoor units • R-410A • EKHBH / EKHBX Options • Altherma • Indoor units...
  • Page 25: Dimensional Drawing & Centre Of Gravity

    Shut off valves (delivered with unit) Thermistor connection (+ sanitary warm water tank) Holes for fixation Blow off drain / drain of drainpan Switchbox connection terminals Wallbracket ≥ 200 ≥ 400 Setup 1 ≥ 350 ≥ 200 Setup 2 3TW56724-1A • Altherma • Indoor units...
  • Page 26: Piping Diagram

    Overview Electric heater body Evaporator Condensor Refr. out Water inlet Refr. in Refrigerant Water side side Refr. in Water outlet Refr. out Check valve Flare connection Screw connection Flange connection Pinched pipe Spinned pipe 3TW56715-1 • Altherma • Indoor units...
  • Page 27: Wiring Diagram

    Wire colour 6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow 3TW56716-5 BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet • Altherma • Indoor units...
  • Page 28 Wire colour 6 BLK: Black / WHT: White / RED: Red / BLU: Blue / PINK: Pink / YLW: Yellow 3TW56716-3B BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange / VIO: Violet • Altherma • Indoor units...
  • Page 29: External Connection Diagram

    NC valve: 3 way valve 2 core 2 core M3S (when EKSWW is installed) R5T - Thermistor water selection sanitary-floorheating temperature Signal Indoor unit Thermistor cable Note: min. distance to power cable = User interface 3TW56719-6 • Altherma • Indoor units...
  • Page 30: Hydraulic Performance

    ESP: External static pressure Flow: waterflow trough the unit Warning: Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrate in the technical specifications. 4TW56749-2 • Altherma • Indoor units...
  • Page 31 ........36 • Altherma • Sanitary Hot Water...
  • Page 32: Features

    E K S R - 4 • Cost effective alternative to a fossil fuel boiler • Easy to install • Low energy bills and low CO2 emissions • Total solution for year round comfort • Altherma • Sanitary Hot Water...
  • Page 33: Specifications

    Cold water in Diameter inch 3/4" FBSP Hot water out Diameter inch 3/4" FBSP 2-2 ELECTRICAL SPECIFICATIONS EKSWW150V3 EKSWW200V3 EKSWW300V3 EKSWW200Z2 EKSWW300Z2 Unit Power Supply Phase 2˜ Frequency Hz Voltage Nominal running current Fuse Size Phase 2˜ • Altherma • Sanitary Hot Water...
  • Page 34: Capacity Tables

    (3) Efficiency of sanitary hot water production: In the ALTHERMA by Daikin system both the heat-pump and the electric booster heater supply the energy to produce sanitary hot water. The higher the portion of energy supplied by the heat-pump, the more energy efficient the system is.
  • Page 35: Dimensional Drawing & Centre Of Gravity

    Water mains in female 3/4’’ BSP Water mains out female 3/4’’ BSP Thermistor connection female 1/2’’ BSP Flow (from hydrobox) female 3/4’’ BSP Return (to hydrobox) female 3/4’’ BSP Switchbox Clixon Connection female 3/4’’ BSP 3TW56714-4 • Altherma • Sanitary Hot Water...
  • Page 36: Wiring Diagram

    3 way valve 2 core 2 core M3S (when EKSWW is installed) R5T - Thermistor water selection sanitary-floorheating temperature Signal Indoor unit Thermistor cable Note: min. distance to power cable = User interface 3TW56719-6 • Altherma • Sanitary Hot Water...