Plumbing Kit Installation - Rinnai Q130SN Installation & Servicing Instructions Manual

High efficiency condensing gas boiler
Table of Contents

Advertisement

Available languages

Available languages

6.1.1
Rinnai supplies specific Plumbing Kits with each boiler type, which must be fitted directly
underneath the boiler on the supply and return pipe. Use of the Rinnai boiler without the
plumbing kit will result in the void of warranty.
To protect the entire heating system we recommend installing a dirt particle trap
i
NOTICE
in the return circuit. When the boiler is installed to an existing heating system this
trap is required. Use of a Y strainer is not permitted as a substitute for a dirt trap.
-
-
-
-
Thoroughly flush all pipes and radiators. We recommend the use of a Rinnai
i
NOTICE
approved system cleaner. Please refer to the list of approved Rinnai system
cleaners in this chapter.
Compression fittings.
Parts:
1. Nut
2. Ferrule
3. Fitting
Fitting instructions:
1
2
3

Plumbing Kit installation

Plumbing Kit installation
Install shut-off valves immediately before and after the dirt particle filter to allow the trap
to be cleaned.
Position 3 (figure 7) is a garden house thread boiler drain that can be used to drain the
boiler or add water treatment additives to the system such as inhibitors or glycol.
Position 4 (figure 7) is the supply connection for an indirect tank when used with the
optional 3-way valve kit.
For information on locating the expansion tank and system fill, please see the Rinnai
Boiler Applications Manual.
-
Refer to the installation template and chapter 5.3 for the pipe connection dimensions.
-
Fit the bronze adapter fittings, supplied with the boiler (fig. 7, pos. 5) first to the
Plumbing Kit and then to the boiler.
1. Push the complete
fitting over the pipe as
far as possible. Ferrule
should be over the
pipe completely.
2. Turn the nut handtight
clockwise.
3. Use 2 wrenches, one
to hold the fitting on
its place, the other
for tighten the nut
clockwise in 3/4 turn.
5
1
2
4
3
6
7
1. Plumbing kit
2. Safety valve
3. Drain and Purge connection
4. DHW flow connection
in case of optional
internal 3 way valve
5. Bronze adapter fittings
6. Service valves
7. Flow
8. Return
9. External pump
8
9
fig. 7
19