Domestic Hot Water - Raypak 503A Installation & Operating Instructions Manual

503a–2003a types h & wh
Table of Contents

Advertisement

Fig. 15: MODE 3 - Single Boiler with Indirect
on Boiler Loop
Mode 3 (Type H Units Only)
This mode selection is for hydronic heating systems
with single or multiple boilers (Maximum 4 boilers) in
primary/secondary piping configuration with or without
Outdoor Air Reset (S4) with indirect DHW on the boil-
er loop (with priority). The system temperature is
controlled by the Supply sensor (S3) whenever the
indirect call for heat is not active. The DHW Supply
sensor (S5) determines the indirect call/tank setpoint.
During an indirect call for heat the boiler firing rate is
determined by the water temperature at the Indirect
Supply sensor (S6) and the Target Max setting when
using the Indirect DHW sensor (S5). The Boiler Pump
(P1) runs during all heat calls regardless of priority.
The Indirect DHW Pump (P3) runs during an indirect
call for heat with no "off" delay. The Boiler Pump (P1)
and System Pump (P2) delay "off" as user defined in
the ADJUST menu. The system pump (P2) runs
whenever the system is enabled for heating and the
outdoor air temperature is lower than the WWSD tem-
perature setting (if utilized) unless an indirect call for
heat is present.
NOTE: A Tank Aquastat can be used in lieu of the
Indirect DHW Sensor (S5). See the Versa IC manu-
al for additional details.

Domestic Hot Water

When designing the water piping system for domestic
hot water applications, water hardness should be con-
sidered. Table G indicates the suggested flow rates for
soft, medium and hard water. Water hardness is ex-
pressed in grains per gallon.
Fig. 16: WH Units - Single Water Heater with Tank
H Units - Single Boiler with Process Tank
WH – Direct DHW Configuration
When the unit is ordered as a "WH" configuration the
only application available to it is direct DHW with sin-
gle or multiple heaters (Maximum 4 heaters). The tank
temperature is controlled by the System sensor (S3).
The Boiler Pump (P1) runs during any call for heat.
The System Pump (P2) output is active whenever the
system is enabled. The Boiler Pump is delayed "off"
after the Tank Target temperature is achieved and as
user defined in the ADJUST menu.
NOTE: WH units will operate to a maximum tank
temperature of 160°F. For temperatures required
above 160°F an "H" model boiler must be used and
great care must be given to ensure water hardness
is no more than 15 grains per gallon for scale free
operation. MODE 1 should be used and configured
for setpoint operation for process heating applica-
tions.
NOTE: If local codes require a vacuum relief valve,
acquire
one
locally
manufacturer's instructions.
17
and
install
per
valve