Brant Radiant Heaters QTD Series User Instruction page 22

Gas-fired infrared quad tube heater
Table of Contents

Advertisement

3.0
Installation
Venting
Rooftop Venting
Guidelines:
Vent Locations and Clearances
• Separate air intake duct from vent pipe a minimum of 4 ft. (1.2 m) by placing vent pipes higher
than adjacent air intake duct.
• Venting may utilize standard B-vent cap.
• The vent terminal must extend a minimum of 2 ft. (.6 m) above the roof.
Figure 3.12
Rooftop Venting - Side View
Vent Cap
Storm Collar
Adjustable Roof Flashing
1 in. Minimum Clearance
1 in. Minimum Clearance
B to C Adapter
Single-Wall Elbow or
Alternate Tee Fitting
Single-Wall Vent
(field supplied)
#8 Sheet Metal Screws
(field supplied)
*Consult the NFPA ANSI Z223.1 Gas Vent Termination criteria if roof pitch exceeds 9:12.
Rooftop Venting
24 in. Min.*
Roof*
Double-Wall B Vent Pipe
Firestop Spacer
Heater
22
QTD
Series

Advertisement

Table of Contents
loading

Table of Contents