Fault
Fault
code
35
BCC missing
36
CRC fault, BCC
37
Incorrect BCC
38
BCC no. invalid
39
BCC system error
41
Flow monitoring
50
Activation of boiler
coding card
52
Activation of boiler
coding card
60
Ionisation current
fluctuates
61
Ionisation current fails
LED constantly red
30 62 555_0709
Troubleshooting
Cause
Boiler coding card was removed
Faulty boiler coding card
The boiler coding card is incompatible with the control
unit PCB
Faulty boiler coding card
Faulty boiler coding card
Return temperature > Flow + 25 K
The boiler coding card must be enabled
The boiler coding card must be enabled
The siphon is blocked, or the flue gas system is
blocked, severe storm
Poor gas quality, monitoring electrode faulty,
severe storm
Ionisation cable shorted out or
ionisation electrode earthed (casing)
Remedy
Fit the correct boiler coding card
Replace boiler coding card
Fit the correct boiler coding card
Replace boiler coding card
Replace boiler coding card
Vent heating system, check system pressure
Check heating circuit pump
Press reset 2 x
Press reset 2 x
Clean siphon, check flue gas system,
check ventilation air, check monitoring
electrode
Check monitoring electrode and cable
Check ionisation cable and position of
electrode to burner. Press reset
61