7. External pressure setting
E.S.P. Control provide required constant air flow rate irrespective of E.S.P. charge.
CAUTION
Installer setting mode is to set the detail function of the remote controller.
If the installer setting mode is not set correctly, it can cause problems to the product, user injury or property damage. This must
be set by an certificated installer, and any installation or change that is carried out by a non-certificated person should be respon-
sible for the results. In this case, free service cannot be provided.
SPEED
TEMP
<Installer Setting Code Table>
1) General air-conditioner product
No.
Function
1
Test Run
2
Address Setting
3
E.S.P. Value
4
Thermistor
5
Ceiling Height
6
Static Pressure
7
Master Setting
Celsius
8
Fahrenheit Switching
j
Some contents may not be displayed depending on the product function
10 _
Ceiling concealed duct - low static pressure
Indoor unit
FAN
OPER
MODE
Code
01
02
03
04
05
06
07
12
1
If you want to set installer setting mode, Press
the Temperature up button and the oper mode
button same time for five seconds.
When you enter the setting mode
2
Initially. Function code is displayed
on the LCD screen.
Value
01:Set
00~FF : Address
<ESP Step>
<ESP Value>
01:VeryLow
0 ~ 255
02:Low
03:Med
04:High
05:Very High
01:Remo
02:Indoor
03:2TH
01:Med
02:Low
03:High
04:Very High
01:V-H
02:F-H
03:V-L
04:F-L
00:Slave
01:Master
00:Celsius
(Optimized only for U.S.A)
01:Fahrenheit
Function Code
Value
<Example>
Function Code
ESP step
ESP value