2. Specifications
Model Name
Power Supply
Capacity
Casing Color
Dimensions
Body
Net Weight
Body
(Row x Column x Fins per inch) x No.
Heat Exchanger
Face Area
Type
Fan
Air Flow Rate
Type
Fan Motor
Output
Running Current
Sound Pressure Level
Sound Power Level
Liquid
Piping
Gas
Connections
Drain (O.D. / I.D.)
Safety Devices
Power and Communication Cable (included Earth) No. x AWG
Model Name
Decoration
Dimensions
Panel
Net weight
Note :
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during opration.
4. Acceptable operating voltage: 187V-253V
2 _
Ceiling cassette 4-way
Indoor unit
V, Ø, Hz
Nominal
kW Class
Nominal
Btu/h Class
-
W x H x D
mm
W x H x D
inch
22-7/16 x 8-7/16 x 22-7/16
kg (lbs)
-
m
2
(ft
2
)
-
H / M / L
m
3
/min
H / M / L
ft
3
/min
-
W x No.
A
H / M / L
dB(A)
Cooling
dB(A)
mm(inch)
mm(inch)
mm(inch)
-
-
Thermal Protector for Fan Motor
-
W x H x D
mm
W x H x D
inch
kg (lbs)
AMNW12GTRA0
[LMCN125HV]
208/230, 1, 60
3.5
12,000
-
570 × 214 × 570
14.0 (30.9)
(2 x 8 x 18) x 1
0.22 (2.40)
Turbo Fan
9.5 / 8.0 / 7.0
335 / 283 / 247
BLDC
43 x 1
0.25
38 / 35 / 32
-
6.35 (1/4)
9.52 (3/8)
32.0(1-1/4) / 25.0(31/32)
Fuse
4C x 18
PT-UQC
700 x 22 x 700
27-9/16 x 7/8 x 27-9/16
3.0 (6.6)
AMNW18GTQA0
[LMCN185HV]
208/230, 1, 60
5.3
18,000
-
570 × 256 × 570
22-7/16 x 10-3/32 x 22-7/16
15.0 (33.1)
(2 x 10 x 18) x 1
0.28 (3.00)
Turbo Fan
13.0 / 12.0 / 11.0
459 / 424 / 388
BLDC
43 x 1
0.25
38 / 37 / 34
-
6.35 (1/4)
12.7 (1/2)
32.0(1-1/4) / 25.0(31/32)
Fuse
Thermal Protector for Fan Motor
4C x 18
PT-UQC
700 x 22 x 700
27-9/16 x 7/8 x 27-9/16
3.0 (6.6)