Dmx Address; Channelmode Nano*Pix 2880 Hp; Channelmode Nano*Pix 1440 Hp; Quiet Mode - LDDE Nano*Pix 1440 HP / 2880 HP User Manual

Rgb+ww+cw
Table of Contents

Advertisement

DMX Address

This menu allocates the DMX start address between 1 and 512.

Channelmode Nano*Pix 2880 HP

Channelmode
5
7
10
60
120
62
30
31
11
121
Activating the control channel adds 1 DMX channel to these addresses.

Channelmode Nano*Pix 1440 HP

Channelmode
5
7
10
30
60
32
15
16
11
61
Activating the control channel adds 1 DMX channel to these addresses.

Quiet Mode

OFF
ON
Rev 7/2014 V4.4
| Specifications subject to change without notice.
R, G, B, joint WW and CW, no master, no strobe
Master, R, G, B, joint WW and CW, strobe
16 bit mode, R, G, B, joint WW and CW, 2 channels, no master, no strobe
R, G, B, WW, CW, no master, no strobe
16 bit mode, R, G, B, WW, CW, 2 channels, no master, no strobe
Master, R, G, B, WW, CW, strobe
R, G, B, WW, CW joined in each upper and lower bank, no master, no strobe
Master, R, G, B, WW, CW joined in each upper and lower bank, no strobe
16 bit mode, R, G, B, joint WW and CW, strobe 8 bit
16 bit mode, R, G, B, WW, CW, strobe 8 bit
R, G, B, joint WW and CW, no master, no strobe
Master, R, G, B, joint WW and CW, strobe
16 bit mode, R, G, B, joint WW and CW, 2 channels, no master, no strobe
R, G, B, WW, CW, no master, no strobe
16 bit mode, R, G, B, WW, CW, 2 channels, no master, no strobe
Master, R, G, B, WW, CW, strobe
R, G, B, WW, CW joined in each upper and lower bank, no master, no strobe
Master, R, G, B, WW, CW joined in each upper and lower bank, no strobe
16 bit mode, R, G, B, joint WW and CW, strobe 8 bit
16 bit mode, R, G, B, WW, CW, strobe 8 bit
Nano*Pix 1440 HP: The cooling fans operate at 100% from temperatures of 40° C
and more and are deactivated for temperatures below 35° C. When temperatures
reach 56° C and above, the master is reduced by a DMX value of 4 per degree of
temperature. Maximum reduction is 96.
Nano*Pix 2880 HP: The cooling fans engage from temperatures of 50° C and above
with the lowest fan stage and are then controlled per degree of temperature. Maximum
fan capacity is reached at temperature of 75° C.
When temperatures reach 56° C and above, the master is reduced by a DMX value of
4 per degree of temperature. Maximum reduction is 96.
Master is set at the maximum value of 159, the cooling fan are deactivated. If
temperature rises above 79° C, cooling fans engage at 100%.