Checking Outputs (Actuators) And Sensors - Viessmann Vitotronic 100 GC1 Installation And Service Instructions Manual

Digital boiler control unit outdoor-reset logic digital cascade control, for installation in custom control panel
Table of Contents

Advertisement

Initial start-up
Further step-by-step instructions

Checking outputs (actuators) and sensors

Vitotronic 100
Relay test
1 2 3 4 5 6 7
The following relay outputs may be selected:
Display
Relay function
indication
11
Burner or stage 1 ON
12
Burner stage 1 and 2 ON or modulation up
13
Burner modulation neutral
14
Burner stage 1 ON (modulation down)
15
Output 20 ON
16
Output 29 ON
17
Output 52 open
18
Output 52 neutral
19
Output 52 close
11
Central fault message ON
Check sensors
1 2 3 4 5 6 7
80
(cont.)
1. Press 9 and
simultaneously for
approx. two seconds.
2. Select the relay outputs
with
or
.
1. Press
.
Scanning operating conditions is
active, see page 88.
2. Scan the actual temperature with
or
.
3. Press
.
3. Press
.
Scanning is completed.