Monessen Hearth DIS33 Installation And Operating Instructions Manual page 12

Natural gas or propane/lpg control type: milli-volt, t-stat, or hi/lo remote control vent-free fireplace systems
Table of Contents

Advertisement

CLEARANCES and HEIGHT REQUIREMENTS
Figure 7 - Measuring Heat Resistant
Material for Mantel
�������
�� �� ����
����������
��������
Figure 9 - Unsafe Mantel Clearance
12
�� �� ����
�� ����
���������
��������
����
������ ��
��������� ��
�������
��
��
��
��
����
HEAT RESISTANT MATERIAL (MINIMUM REQUIRE-
MENTS) WITH NO WOODEN MANTEL OR OTHER COM-
BUSTIBLE PROJECTION
Heat resistant material (minimum requirements) with wooden
mantel or other combustible projection:
To install the heater with a wooden mantel shelf or other combustible
projection above, first measure the heat resistant material shown
in Figure 7.
���
���
��
��
Figure 8 - Minimum Mantel Clearance
Figure 9 is an example of an unsafe mantel installation. The
mantel projects 4" at 8" above the opening, exceeding the
maximum acceptable distance of 2
8" at 10" above the opening, exceeding the maximum acceptable
distance of 6".
If your mantel profile is unsafe, you may either:
• Raise the mantel to an acceptable height or,
���
• Remove the mantel.
���
Example: A mantel
���
may project from the
wall a maximum of 2
���
at minimum of 8" above
��
the opening, and a maxi-
mum of 12" at a mini-
mum of 26" above the
opening.
1
/
". The mantel also projects
2
1
/
"
2
26D3311