Marshall-Tufflex e-Tracker Operating & Maintenance Manual page 9

Portable energy monitor
Table of Contents

Advertisement

6)
ID ERR 3
--
MTH-DAY
HRS-MINS
2011
07.14
10.40
(2 messages flashing)
Non specific connection error
7)
LO INPUT
LO LO LO
MTH-
07.14
10.40
(2 messages flashing)
Signal from CTs insufficient for automatic phase sensing, proceed to manual
setup routine
LO indicates which channel(s) has insufficient signal.
Increase phase current if possible, switch off, switch on (after 5 seconds) and try again.
Manual set up routine
Switch off e-Tracker, plug in EV-Trac probe and switch on after 5 seconds.
The SELF TEST routine starts.
Followed by:
PROBE SCAN
NO SIGNAL
MTH-
07.14
10.40
Place the Probe along the phase cables' insulation one at a time. Display indicates L1
or L2 or L3, clip-on the appropriate CT as below.
Red CT on phase indicated as L1 (ignore phase cable colour)
Yellow CT on phase indicated as L2
Blue CT on phase indicated as L3.
If 'SIG ERR' displayed move Probe to different location on cable, away from other
phase cables.
Press enter
NOT FOUND
--
--
2011
USE PROBE
LO LO LO
MTH
2011
07.14
2011
e-Tracker portable energy monitor operating and maintenance manual
--
MTH-DAY
HRS-MINS
07.14
10.40
2012011
10.40
9