Connecting leads shall not be installed in the same conduit as the AC supply wiring, communication cables or data
cables.
Connecting leads and electric animal fence wires shall not cross above overhead power or communication lines.
Crossings with overhead power lines shall be avoided wherever possible. If such a crossing cannot be avoided it shall
be made underneath the power line and as nearly as possible at right angles to it.
If connecting leads and electric animal fence wires are installed near an overhead power line, the clearances shall not
be less than those shown in the table below.
Minimum clearances from power lines for electric animal fences
Power line voltage
1000 V
1000 V to 33,000 V
33,000 V
If connecting leads and electric animal fence wires are installed near an overhead power line, their height above the
ground shall not exceed 10' (3 m). This height applies to either side of the orthogonal projection of the outermost
conductors of the power line on the ground surface, for a distance of:
6'6" (2 m) for power lines operating at a nominal voltage not exceeding 1000 V.
50' (15 m) for power lines operating at a nominal voltage exceeding 1000 V.
Electric animal fences intended for deterring birds, household pet containment or training animals such as cows need
only be supplied from low output units to obtain satisfactory and safe performance.
Clearance
10 ' (3 m)
13' (4 m)
27' (8 m)