Indoor Unit Installation - Daikin FXLQ20P2VEB Installation And Operation Manual

Daikin vrv system air conditioners
Hide thumbs Also See for FXLQ20P2VEB:
Table of Contents

Advertisement

Indoor unit installation

As for the parts to be used for installation work, be sure to use the
provided accessories and specified parts designated by our
company.
Make sure wiring, piping and drain piping meets your customer's
requirements and must comply with local and national regulations.
Ensure the unit is level when installed so that drainage
flows smoothly. If inclined, water can leak.
How to open and close the front panel
(for FXLQ units only)
To open the front panel, remove 4 screws from the corner pieces,
unhook the corner pieces and remove the front panel as shown in the
figure below.
1
To close the front panel, use the opposite method.
Floorstanding installation
Make sure that the floor is strong enough to bear the unit
weight.
1
Level the indoor unit with the
leveling screws (accessory part).
If the floor is too uneven to level
the unit, place the unit on a flat
and level base.
2
If the unit is in danger of falling over, either fasten to the wall
using the holes provided, or fasten to the floor with a field
supplied floor fastener.
FXLQ20~63P2VEB + FXNQ20~63P2VEB
VRV System air conditioners
4P323720-1 – 2012.06
Wallmounted installation
1
1
2
2
2
2
2
1
1
Check whether the wall is strong enough to bear the
weight of the unit. If there is a risk, reinforce the wall
before installing the unit.
Use the installation mount on the rear of the unit for
installation.
The unit requires minimum 100 mm
clearance on the bottomside for air
intake
and
maximum
clearance from the wall by using
spacers (field supply).
Positioning of holes for fastening to the wall.
Unit of measurement = mm.
205
Model
A (mm)
20 + 25
590
32 + 40
730
50 + 63
1010
The legs can be removed if the indoor unit is to be hung on a
wall. To do so, remove the legs and mount the 2 decorationstrips
to the corner pieces as shown in the figures below.
 For FXLQ units only
1
5
4
5
≤20
20 mm
A
100≤
≤200
A
205
1
4
Installation and operation manual
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents