Important Information Regarding The Refrigerant Used; Selecting Installation Site - Daikin FXLQ20P2VEB Installation And Operation Manual

Daikin vrv system air conditioners
Hide thumbs Also See for FXLQ20P2VEB:
Table of Contents

Advertisement

Accessories
Check if the following accessories are included with your unit.
1
2
3
4
1x
1x
4x
1x
1
Metal clamp
2
Drain hose
3
Leveling screw
4
Sealing pad
5
Insulation for gas pipe
Optional accessories
There are two types of remote controllers: wired and wireless.
Select a remote controller according to customer request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.
For the following items, take special care during
construction and check after installation is finished
Tick
when
checked
Is the indoor unit fixed firmly?
The unit may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling or heating.
Is the unit fully insulated and checked for air leaks?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the
name plate?
The unit may malfunction or components may burn out.
Are wiring and piping correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded?
Dangerous at electric leakage.
Is the wiring size according to specifications?
The unit may malfunction or components may burn out.
Is nothing blocking the air outlet or inlet of either the indoor or
outdoor units?
It may result in insufficient cooling or heating.
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system might not be clear.
Notes to the installer
Read this manual carefully to ensure correct installation. Be sure
to instruct the customer how to properly operate the system and
show him/her the enclosed operation manual.
Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.
This unit can be installed on the floor or be mounted to a wall.
FXLQ20~63P2VEB + FXNQ20~63P2VEB
VRV System air conditioners
4P323720-1 – 2012.06
5
6
7
8
1x
1x
8x
1x
6
Insulation for liquid pipe
7
Clamp
8
Installation and operation
manual
Important information regarding the
refrigerant used
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.
Refrigerant type:
R410A
(1)
GWP
value:
1975
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

Selecting installation site

1
Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.
-
The installation location is frost-free.
-
Where optimum air distribution can be ensured.
-
Where nothing blocks air passage.
-
Where condensate water can be properly drained.
-
Where the floor or wall is strong enough to bear the indoor
unit weight.
-
Where sufficient clearance for maintenance and service can
be ensured.
-
Where piping between indoor and outdoor units is possible
within the allowable limit. (Refer to the installation manual of
the outdoor unit.)
-
This is a class A product. In a domestic environment this
product may cause radio interference in which case the user
may be required to take adequate measures.
-
Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and noise in
those electrical appliances. (Noise may be generated
depending on the conditions under which the electric wave is
generated, even if 1 meter is kept.)
-
When installing the wireless remote controller kit, the
communication distance between wireless remote controller
and indoor unit might be shorter if there are fluorescent lights
who are electrically started in the room. The indoor unit must
be installed as far as possible away from fluorescent lights.
-
Do not place objects that are susceptible to moisture directly
beneath the indoor or outdoor units. Under certain conditions,
condensation on the main unit or refrigerant pipes, air filter
dirt or drain blockage may cause dripping, resulting in fouling
or failure of the object concerned.
Installation and operation manual
2

Hide quick links:

Advertisement

Table of Contents
loading