Tadiran Telecom TGL-9 Installation Instructions

Tadiran Telecom TGL-9 Installation Instructions

Tadiran tgl/dgl air conditioners installation instructions

Advertisement

Quick Links

General
These instructions are intended as general guidelines. The air conditioner must be installed by trained and authorized personnel.
Use the following size copper tubing for connecting the outdoor and indoor units:
Models TGL/DGL 9, 11 - 3/8" and 1/4". Models TGL/DGL 15, 20, 25 - 1/4" and 1/2". Models TGL 30 - 3/8" and 5/8".
Installation must be performed in accordance with the manufacturer's specifications, using only approved tubing, original electrical
cables and accessories.

Standard Accessories

Mounting Bracket
Absorption cushions
for DGL and TGL 25-30

Electrical Requirements

The air conditioner must be directly connected to an
appropriate power source.
Use 16A fuses for all Models TGL/DGL air conditioners.
Use a single-length power cable, without extensions.
When installing a Dual System air-conditioner of DGL
series (a single outdoor unit and two separate indoor units)
both indoor units must be connected to the mains power supply in order for the system to function properly.
Indoor and Outdoor Unit Location
The indoor and outdoor units should be installed as
close to each other as possible. Do not exceed the tubing
lengths and height differences which appear in the accompanying
table above:

Outdoor Unit

Make sure to leave sufficient space around the unit. See Figure 1 for
minimum required distances between the unit and nearby walls.
Install the unit in a location with convenient access for service and
maintenance purposes.
Position the unit to minimize motor noise which reaches the customer
and neighbors.
In heating mode, water can form in the condenser. A drainage hose may
be attached to the unit. Use the adapter shown Figure 1.
For opening service door in models TGL 9-20, keep a minimum distance of
0.27m (10" 62') between the unit and the support's end.
Make sure of installing the unit legs to the support.

Indoor Unit

Make sure to leave sufficient space around the unit. See Figure 2 for minimum
required distances between the unit and the ceiling, floor and surrounding walls.
Locate the unit to ensure free air flow around it.
A 120 cm. power cable is supplied with the unit. We recommend placing the power
outlet near the unit, on its right side.
Avoid installing the unit near a
source of heat, such as direct
sunlight, steam or a flame.
Install the unit in a location
with convenient access to
refrigerant line connections
for service and maintenance
purposes.
TGL/DGL Installation Instructions
Electrical terminal block
Drain hose adapter
for≠ ≠ ≠ ≠ ≠ DGL/TGL 25-30
Outdoor sensor
connecting cable
Indoor
Dimensions
mm (")
a
b
c
6/7 stations according
to the model
Drain hose adapter
for≠ ≠ ≠ ≠ ≠ DGL/TGL 9-20
Insulation for Fittings
Model
TGL-9, 11, 15, 20, 25, 30
DGL-9, 11, 15, 20
DGL-11/15
0.15m(6")
min.
0.6m(2')
min.
c
Model
TGL 9-20
TGL 25-30
185 (32.3")
185 (45.3")
260 (12.6")
295 (13.8")
815 (6.7")
1080 (7.9")
50Hz TAC 505 TAC 506 0600
Long Screws
Remote Controller
Wall Plugs
User's Manual
Remote Controller Rack
Maximum tubing
length in meters (ft)
difference between unit
15 (49')
15 (49')
15 (49')
Insert the
drainage adapter
from the outside of
the outdoor unit
a
0.6m(2')
min.
0.15m(6")
min.
0.15m(6")
min.
0.6m(2')
min.
0 . 6
m (
2 ' )
m i
b
n .
TGL 9-20
Outdoor
Dimensions
TGL 9-20
mm (")
DGL ALL
a
320 (32.3")
b
641 (12.6")
c
1100 (6.7")
0.15m (6") min.
0.2m
b
(8")
min.
1.8−2.5m
(6'-8'3") min.
Fig. 2
TGL - 51302613575
S TA R T
S T O P
1 2 3 S L E E P
D A I LY
M O D E
FA N
S W E E P
WIRELESS DIGITAL REMOTE CONTROLLER
WIRELESS DIGITAL REMOTE CONTROLLER
and Batteries
WIRELESS DIGITAL REMOTE CONTROLLER
Maximum height
WIRELESS DIGITAL REMOTE CONTROLLER
in meters (ft)
10 (33')
10 (33')
10 (33')
Insert the
drainage adapter
from the inside of
the outdoor unit
a
0.6m(2')
min.
0.15m(6")
min.
0.6m(2')
min.
b
c
DGL, TGL 25-30
Model
TGL 25-30
Plastic Model
265 (45.3")
540 (13.8")
730 (7.9")
Fig. 1
a
0.2m
(8")
min.
c

Advertisement

loading

Summary of Contents for Tadiran Telecom TGL-9

  • Page 1: Standard Accessories

    The air conditioner must be directly connected to an in meters (ft) appropriate power source. TGL-9, 11, 15, 20, 25, 30 15 (49') 10 (33') Use 16A fuses for all Models TGL/DGL air conditioners. DGL-9, 11, 15, 20...
  • Page 2: Installing The Indoor Unit

    Installing the Indoor Unit Refrigerant line routing The refrigerant lines may be routed in any of the four directions shown in Figure 3. Installing the mounting bracket Pull out the mounting bracket attached to the back of the unit. See Figure 4. Position the mounting bracket on the wall and level it using a spirit level.
  • Page 3: Installing The Outdoor Unit

    Piping and Display Cable Connect the ends of the refrigerant lines to their appropriate fittings, following the guidelines in the "Connecting the refrigerant lines" section. Make sure the drainage hose is at the bottom side of the wall through-hole (see Figure 6). Connect the cable labeled "Display"...
  • Page 4: Finishing The Job

    Do not open service valves or remove protective caps from tubing ends until all the connections are made. Take care to avoid kinks or flattening of the tubing. Bend tubing with special bending tools to avoid the formation of sharp bends. Keep the tubing free of dirt, sand, moisture and other contaminants to avoid damaging the refrigerant system.