Procedures Of Wiring; Wiring Of The Outdoor Unit - Hitachi RAS-60YHA2+ Installation Manual

Indoor unit outdoor unit split-unit air conditioner
Hide thumbs Also See for RAS-60YHA2+:

Advertisement

Please mount the Outdoor unit on stable ground to prevent vibration
G
and increase of noise level.
Decide the location for piping after sorting out the different types of
G
pipe available.
When removing side cover, please pull the handle after undoing the
G
hook by pulling it downward.
Please face this side (suction
side) of the unit to the wall.
Please remove side cover
when connecting the piping
and connecting cord.
Pull downward
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There are holes on the base of Outdoor unit for condensed
water to exhaust.
In order to flow condensed water to the drain, the unit is installed on a
stand or a block so that the unit is 100mm above the ground as shown
figure. Join the drain pipe to one hole.
At first insert one portion of the hook to the base (Portion A), then pull the
drain pipe in the direction shown by the arrow while inserting the hook
into the base. After installation, check whether the drain pipe cling to the
base firmly.
A
BASE
DRAIN PIPE
BUSH
10
When Using and Installing In Cold Areas
When the air conditioner is used in low temperature and in snowy
conditions, water from the heat exchanger may freeze on the base surface
to cause poor drainage. When using the air conditioner in such areas, do
not install the bushings. Keep a minimum of 250mm between the drain
hole and the ground. When using the drain pipe, consult your sales agent.
For more details, refer to the installation Manual for Cold Areas.
G
THIS APPLIANCE MUST
!
WARNING
BE EARTHED.

Procedures of Wiring

Power is supplied from Outdoor Unit
Indoor Unit
Outdoor Unit
L
N
A
B
C
D
A
B
C
D
AC 240V
Connecting Cord
Power line
Control line
30mm
30mm
10mm
10mm
Indoor
Unit
10mm
GRN + YEL
70mm
Strip wires
35mm
25mm
Outdoor
10mm
10mm
Unit
10mm
GRN + YEL
45mm
!
WARNING
G
The naked part of the wire core should be 10 mm and fix
it to the terminal tightly. Then try to pull the individual wire
to check if the contact is tight. Improper insertion may
burn the terminal.
Be sure to use only power cables approved from the
G
authorities in your country. For example in Germany: Cable
type: NYM 3x1.5mm
2
, (fuse = 20A time delay)
Please refer to the installation manual for wire connection
G
to the terminals of the units. The cabling must meet the
standards of electrical installation.
G
There is a AC voltage of 240V between the L and N
terminals. Therefore, before servicing, be sure to remove
the plug from the AC outlet or switch off the main switch.
1
Insulation And Maintenance Of Pipe Connection
G
The connected terminals should be completely sealed with
heat insulator and then tied up with rubber strap.
G
Please tie the pipe and power line together with vinyl tape as
shown in the figure showing the installation of Indoor and
Outdoor units. Then fix their position with holders.
To enchance the heat insulation and to prevent water
G
condensation, please cover the outdoor part of the drain hose
and pipe with insulation pipe.
G
Completely seal any gap with putty.
Insulation material for pipe connection
Sleeve of
protection pipe
Putty
Putty
3
Power Source And Operation Test
Power Source
CAUTION
!
G
Please use a new socket. Accident may occur due to the use of old
socket because of poor contact.
G
Please plug in and then remove the plug for 2 – 3 times. This is to
ensure that the plug is completely plugged into the socket.
G
Keep additional length for the power cord and do not render the
plug under external force as this may cause poor contact.
G
Do not fix the power cord with U-shape nail.
<
>
IA534: A
Ins RAC-60YHA2 (2)
1
Black
1
Preparation of Pipe
Use a pipe cutter to cut the copper pipe.
G
G
Jagged edge will cause leakage.
G
Point the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.
G
Before flaring, please put on the flare nut.
Die
Outer
Diameter (mm)
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
2
Pipe Connection
G
Please be careful when bending the copper pipe.
G
Applied frozen grease to the connection points and then screw in manually. After that,
use a torque wrench to tighten the connection.
9
BUSH
11
DRAIN PIPE
Flare nut
Torque
Wrench
wrench
Wiring Of The Indoor Unit
G
For wire connection of the Indoor unit, you need to remove
front panel and electrical cover.
Method to remove front panel
Refer to "How to Remove The Front Cover".
G
Method to remove electrical cover
G
Remove the screw
and electrical cover.
G
Insert the
connecting cord
(A,B,C,D) from the
bottom of unit.
G
Fixed the wire to
Screw
terminal wires
firmly as shown in
AUTO
RESTART
SWITCH
figure at right side.

Wiring Of The Outdoor Unit

G
Please remove the side cover for wire connection.
G
You may not be able to close the side
cover due to the connecting cord, under
such situation, please press against the
!
wall of side cover to fix it.
WARNING
G
Be sure that the hooks (6 places) are
plugged in.
Otherwise, water leakage may occur and
this causes short circuit or faults.
Checking for the electric source
and the voltage range
G
Before installation, the power source must be checked and
necessary wiring work must be completed. To make the
proper wiring capacity, use the wire gauges list below for
the lead-in from a pole transformer and for the wiring from a
switch board of fuse box to the outlet in consideration of the
locked rotor current.
IMPORTANT
Cable length
Wire cross-section
up to 16m
1.5mm
up to 15m
2.5mm
up to 25m
4.0mm
2
Installation Of Remote Controller
The remote controller can be placed in its holder which is
G
fixed on wall or beam.
G
To operate the remote controller at its holder, please ensure
that the unit can receive signal transmitted from the controller
at the place where the holder is to be fixed. The unit will beep
when signal is received from the remote controller. The signal
transmission is weaken by the fluorescent light. Therefore,
during the installation of the remote control holder, please
switch on the light, even during day time, to determine the
mounting location of the holder.
The controller must
be hooked onto the
hook at the lower
Screw (2 pieces)
part of the holder.
Push in the remote
controller in the
direction as shown
Holder for
in figure below.
Remote Controller
Remote
Controller
Operation Test
G
Please ensure that the air conditioner is in normal
operating condition during the operation test.
G
Explain to your customer the proper operation
procedures as described in the user's manual.
Trimming tool
Copper pipe
!
CAUTION
Die
A
Copper pipe
A (mm) Rigid Flaring Tool
For R410A tool
For R22 tool
~
0.0
0.5
1.0
~
0.0
0.5
1.0
~
0.0
0.5
1.0
Outer
Torque N·m
dia.of pipe
(kgf · cm)
Small dia. side
6.35 (1/4")
13.7 – 18.6 (140 – 190)
Large dia. side
9.52 (3/8")
34.3 – 44.1 (350 – 450)
12.7 (1/2")
44.1 – 53.9 (450 – 550)
Valve
Small dia. side
6.35 (1/4")
19.6 – 24.5 (200 ~ 250)
head cap
Large dia. side
9.52 (3/8")
19.6 – 24.5 (200 ~ 250)
12.7 (1/2")
29.4 – 34.3 (300 – 350)
Valve core cap
12.3 – 15.7 (125 ~ 160)
Connect the
earth cord
A
B
C
Electrical
cover
After remove the screw
and band, put the
connecting cords and fix
the band with screw.
N
L
A
B
G
Investigate the power supply capacity and other
electrical conditions at the installation location.
Depending on the model of room air conditioner to
be installed, request the customer to make
arrangements for the necessary electrical work etc.
The electrical work includes the wiring work up the
outlet. In localities where electrical conditions are
poor, use of a voltage regulation is recommended.
IMPORTANT
Fuse Capacity
20A time delay fuse
CAUTION
2
Outdoor supply cords shall not be lighter than
2
polychloroprene sheathed flexible cord with code
2
designation 60245 IEC 57.
How to Remove The Front Cover
1 Remove the front panel.
Please remove and attach the front panel by both hands.
G
2
After opening the front panel by both hands.
G
1 1 1 1 1
Undo the right arm while pushing it inside.
2 2 2 2 2
Slide the front panel to right as shown in figure. Then
remove while pulling it to front.
2 Remove the filters.
Cap
3 Remove the caps and
screws at the lower portion
of the front cover.
Screw
4 Pull the front cover upward
as far as the location where
the lower portion of the front
cover is on the deflector.
Lower portion of front cover
5 Remove while pulling the front
cover in direction to arrow as
shown in figure to hold the both
sides of front cover.
12/24/08, 10:50
3
Removal Of Air From The Pipe And Gas Leakage Inspection
Procedures of using Vacuum Pump for Air Removal
When the meter reaches –101KPa (–76cmHg)
As shown in figure on the right,
during pumping, fully tighten the shuttle.
remove the cap of valve head and
1
valve core and then connect them
to the vacuum pump and manifold
valve.
Fully tighten the "Hi" shuttle of the
manifold valve and completely
unscrew the "Lo" shuttle. Run the
2
Charge
vacuum pump for about 10–15
hose
minutes, then completely tighten the
"Lo" shuttle and switch off the
When pumping starts, slightly loosen
vacuum pump.
the flare nut to check of air sucked in.
Then tighten the flare nut.
Completely unscrew the spindle of
the service valve (at 2 places) in
3
anti-clockwise direction to allow the
flow of coolant (using Hexagonal
Wrench key).
Remove the Charge hose and
tighten the cap of valve head. The
Cap of valve head
4
task is then completed.
Gas Leakage Inspection
Please use gas leakage detector to check if
leakage occurs at the connection of Flare nut
as shown on the right.
If gas leakage occurs, further tighten the
connection to stop leakage.
In case of removing Flare nut of a cooling unit, first remove a
!
CAUTION
nut of small diameter side, or else seal cap of big diameter side
will fly out.
How To Connect The Optional Parts
(RAC Adapter, Weekly Timer, Wired Remote Control)
Weekly timer/
D
Wired remote controller
Weekly timer / Wired
remote controller
CN1102
C
D
RAC
Adaptor
cord
Earth terminal
H-LINK
[For all optional part, please refer catalog for part number]
As for connecting to H-Link, a separately purchased
RAC Adapter is required.
G
To install the wiring the electrical box cover must be opened.
Connect the connector of RAC adapter to CN1101.
G
G
Assemble back the cover of electrical box.
G
Please refer to the respective user manual of RAC Adapter
for further details.
G
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
WEEKLY TIMER / WIRED REMOTE CONTROLLER
[For all optional part, please refer catalog for part number]
Connection to the electrical box:
G
Remove the cover of electrical box.
Connect the connector of Weekly Timer/wired remote
G
controller to CN1102.
Assemble back the cover of electrical box.
G
G
Please refer to the respective user manual of Weekly Timer/
wired remote controller for further details.
G
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
How to Attach the Front Cover
1 1 1 1 1
After covering the front cover to the unit, certainly hook at
the upper portion (three places). Then, check that the drain
pan is certainly attached. Push the center of front cover in
the direction of arrow.
1
2 2 2 2 2
Fix the front cover at lower portion by screws and attach
the caps.
3 3 3 3 3
Attach the front panel.
Certainly insert the left shaft of the front panel to the hole
G
of the front cover. Next insert the right shaft as same as
the left.
4 4 4 4 4
Attach the filters which are placed the surface written
"FRONT" up.
Deflector
After attaching the filters, push the front panel at three
G
arrow portion as shown in figure and close it.
Meter showing pressure
Lo
Hi
Manifold valve
Vacuum pump
The body of
service valve
Cap of
valve core
Hexagonal
Wrench Key
Cap of valve head
RAC Adapter
CN1101
Hole
Shaft
Guide