12.1.5 Tank Mode Operation
Control contents:
3 ways valve direction
- 3 ways valve switch and fix to tank side.
Heat pump Thermostat characteristic
- Water set temperature = Tank set temperature or [51°C] whichever lower.
- Heat pump Water Outlet set temperature is set to Maximum (53°C) at tank mode.
i. Case 1
- THERMO OFF TEMP:
1
THERMO OFF TEMP = Water set temperature + [0°C].
2
Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump OFF, water pump OFF.
- THERMO ON TEMP:
1
THERMO ON TEMP = Water set temperature + [-2°C].
When detect tank temperature < THERMO ON TEMP, water pump ON for 3 minutes then heat pump ON.
ii. Case 2
- Heatpump THERMO OFF TEMP:
1
Heat pump THERMO OFF TEMP = 55°C + [+2°C].
2
Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump OFF.
- Heatpump THERMO ON TEMP:
1
Heat pump THERMO ON TEMP = Water inlet during thermo off time + [-3°C].
2
Heat pump ON back when water outlet temperature < Heat pump THERMO ON TEMP.
iii. Case 3
- Heat pump THERMO OFF TEMP:
1
Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
- Heat pump THERMO ON TEMP:
1
Heat pump THERMO ON TEMP = Water inlet temperature < 55°C.
Booster heater control
- Booster heater turn On and Off follow normal operation.
- Booster heater turn ON condition:
1
During startup time (initialization), Booster heater turn ON after DELAY TIMER.
2
When tank temperature lower than HEATER ON TEMP
3
20 minutes from previous heater off.
- Booster heater turn OFF condition:
1
When tank temperature higher than tank set temperature for continuous 15 secs.
Solar 3 way valve
- Solar pump operates follow solar operation specification.
2 way valve closes
Others
- Indoor backup heater cannot be ON during tank mode only.
40