Piping Method - Fujitsu AJ*A72LALH Series Installation Manual

Vrf system outdoor unit
Table of Contents

Advertisement

Main pipe
To indoor unit
Main pipe
To indoor unit
Do not connect a separation tube after a header.
Leave the distance 0.5 m or more for straight part to branch tube and header.
For details, refer to the Installation Instruction Sheet of each part.
5. 3.

Piping method

5. 3. 1.
Opening the knockout hole
Be careful to prevent panel deformed or damaged while opening the knockout hole.
To prevent cutting of the wiring after the knockout hole was opened, remove the burrs along the edge.
In addition, to prevent rusting, painting the edge with rust preventive paint is recommended.
The piping can be connected from 2 directions; the front or the bottom.
(Knockout holes are provided so that the piping can be connected from 2 different directions.)
Use the front knockout hole, as required.
Fig.
A Knockout position
En-14
0.5m or more
Separation tube
or
Header
0.5m or more
To indoor unit
Fig.
B Detail of knockout po-
sition (bottom)
CAUTION
0.5m or more
To indoor
unit
0.5m or more
CAUTION
Fig.
(front)
(Unit: mm)
Knockout hole
Separation tube
To indoor
unit
or
Header
To indoor unit
C Detail of knockout position
(Unit: mm)
Knockout
hole