Number
220001
The tag is not downloaded because the associated
channel/the unit does not support downloading the
data type bool/bit.
220002
The tag is not downloaded because the associated
channel/the unit does not support downloading the
data type byte.
220003
The associated driver could not be uploaded. It is
possible that the driver is not installed.
220004
Communication is terminated and no update is
executed because the cable is not connected or is
defect etc.
220005
Communication is running.
230000
The value entered could not be accepted. The
entered value is rejected and the previous value is
specified again.
Either the value range has been exceeded or
impermissible characters were entered.
230002
Since the current password level is inadequate or the
password dialog box was closed with ESC, the entry
is rejected and the previous value is specified again.
230003
Changeover to the specified screen is not executed
because the screen is not available/configured. The
current screen remains selected.
3)
240000
Runtime is operating in Demo mode.
There is either no Stopcopy license or it is defect.
3)
240001
Runtime is operating in Demo mode.
Too many tags are configured for the installed version.
3)
240002
Runtime is operating with a time-limited standby
authorization.
240003
Authorization cannot be executed.
ProTool/Pro RT is running in Demo mode.
240004
Error during reading the the standby authorization.
ProTool/Pro RT is running in Demo mode.
250000
The tag in the specified line in Status/Control is not
updated because the address configured for this tag
is not available.
250001
The tag in the specified line in Status/Control is not
updated because the PLC type configured for this tag
is not available.
250002
The tag in the specified line in Status/Control is not
updated because it is not possible to map the PLC
type in the tag type.
260001
A password has been entered which is unknown to
the system. Therefore, the lowest password level has
been set. This corresponds to the status following
Logout .
MP270 Equipment Manual
Release 01/99
Effect/Cause
System Messages
Remedy
Change the configuration.
Change the configuration.
Install the driver by re-installing
ProTool/Pro RT.
Check the connection.
Enter a permissible value.
Activate an adequate password
level using Login.
Configure the screen.
Check the selection function.
Load the license.
Load an adequate license /
powerpack.
Restore the full authorization.
Restart ProTool/Pro RT or reinstall
it.
Restart Sie ProTool/Pro RT, install
the authorization or repair the
authorization (see Commissioning
Instructions Software Protection).
Check the set address and then
check that the address has been
set up in the PLC.
Check the set address.
Check the set address.
Enter a known password in the
password input field (with
corresponding level).
C-11