Insulation of Refrigerant Tubing

IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
After a tube has been insulated,
CAUTION
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Outdoor Unit
Outdoor Unit
Muffler
Outdoor Unit
Outdoor Unit
Wide tube
service
Muffler
Wide tube
valve
O.D.
ø15.88 mm
(5/8 ")
Narrow
tube
service
Narrow tube
valve
Capillary tube
O.D.
ø6.35 mm
(1/4")
Check port
GRV180L7TAA
GRV220L7TAA
Compressor
Accumulator
Capillary for
liquid injection
Strainer
Thickness:
Min. 8 mm
Wide tube
27
Insulation
Thickness:
Min. 8 mm
Narrow tube