Monitor 4221441 Component Voltage Readings - Monitor 422 Service Manual

Monitor heating systems
Table of Contents

Advertisement

MONITOR HEATING SYSTEMS
Section 6:
Troubleshooting
Monitor 4221441 Component Voltage Readings
COMPONENT
READING TAKEN AT
A C
DC
Thermistor
Q on PCB Sensor disconnected
5
- - -
Thermistor
Q on PCB Sensor connected
1.53.2
Air Pressure Switch,'
Connector J
1 1 0
Overheat Protector Closed
Air Pressure
Switch,'
Connector J
0
Overheat Protector Open
Damper Solenold
I on PCB
105
Solenoid Pump
K on
PCB
pulse'
C~rculat~on Fan High
Speed
RD
to BK(M-422)
110
WH to BK(M-441)
110
Circulation Fan Low Speed
RD to
BK(M-422)
93
WH to BK(M-441)
9 l
Igniter
B on
PCB
110
Power Transformer
AC 120V
110
(primary
side)
Power Transformer
AC 120V
120
(secondary s~de)
AC 12V
12
Combustion Blower
F on PCB
110
I
High Speed
Combust~on Blower
F on
PCB
921M-422)
Low
Speed
(Ql is Off)
~ ~ ( ~ - 4 4 1 )
Res~stor
G on PCB
1WM-422)
22(M41)
*Pulse can only be measured with a hlgh
impedance
d~gltal volt meter.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

22214144140

Table of Contents