Sanyo SAP-KRV9AEH Installation Instructions Manual page 8

Inverter split system air conditioner
Hide thumbs Also See for SAP-KRV9AEH:
Table of Contents

Advertisement

3-4-2. Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to local elec-
trical codes. Carefully observe these regulations when carrying out the installation.
Listed in the tables below are the recommended and maximum allowable wire lengths and diameters for the power
supply system. Please refer to the wiring system diagram (Fig. 19) for the meaning of "A", "B", and "C" in Table 1.
Table 1
Cross-Sectional
2
Area (mm
)
Model
KRV9AEH
KRV12AEH
G
CAUTION
G
WARNING
Be sure to comply with local codes on
G
running the wire from the indoor unit
to the outdoor unit (size of wire and
wiring method, etc.).
Each wire must be firmly connected.
G
No wire should be allowed to touch
G
refrigerant tubing, the compressor, or
any moving part.
WARNING
To avoid the risk of electric shock, each air conditioner unit must be grounded.
G
For the installation of a grounding device, please observe local electrical codes.
G
Grounding is necessary, especially for units using inverter circuits, in order to release charged elec-
G
tricity and electrical noise caused by high tension. Otherwise, electrical shock may occur.
Place a dedicated ground more than 2 meters away from other grounds and do not have it shared
G
with other electric appliances.
(A) Power Supply Wiring Length (m)
(B) Power Line Length (m)
2
(A) 1.5 mm
1.8 m
1.8 m
Be sure to connect the
power supply line to the
indoor unit as shown in the
wiring diagram. The outdoor
unit draws its power from
the indoor unit.
Do not run wiring for anten-
na, signal, or power lines of
television, radio, stereo,
telephone, security system,
or intercom any closer than
1 meter from the power
cable and wires between the
indoor and outdoor units.
Electrical noise may affect
the operation.
(C) Control
Line Length (m)
2
(B) 1.5 mm
1.5 mm
15.0 m
15.0 m
15.0 m
15.0 m
WIRING SYSTEM DIAGRAM
OUTDOOR
UNIT
Terminal
N ( 1 )
(C)
2
3
(Grounding line)
Power supply
Single-phase
220 − 240 VAC, 50 Hz
8
Fuse or Circuit
Breaker Capacity
2
15A
INDOOR
UNIT
(B)
Terminal
N ( 1 )
2
3
(A)
L
L
N
N
P.C.B
Grounding line
Fig. 19