INSTALLATION

UNPACKING AND INSPECTION
1. Cabinet keys are attached, by ty-rap, to side of
humidifier.
2. Open the cabinet and check for concealed shipping
damage. Report any damage immediately to the
carrier who delivered the shipment.
3. The following components are packed in a shipping
carton for connection when installing the humidifier.
A. Distribution pipe.
B. Steam hose.
C. Condensate return line.
4. Optional accessories may be packed with the cabinet
or in the same shipping carton. Large accessories may
ship in separate cartons.
5. Inside the cabinet is an envelope containing the
following items:
A. Steam hose clamps.
B. Condensate return line clamps.
C. Drain pipe fitting.
D. Installation, operation and maintenance manual,
yellow caution sheet for hose routing, replacement
parts list and spec sheet.
MOUNTING THE HUMIDIFIER
Locate the humidifier cabinet level and plumb, using the
level screws (Photo B) on a surface as close to the steam
distributor as possible at a convenient height for servicing.
Allow 12" or more on each side for panel access and 16"
from the bottom of the unit to floor to allow for drain connec-
tions. If there is no common drain within close proximity of
humidifier, a drain pump (Carnes HXWA) may be required
to accommodate this distance. Allow 18"-38" respectively,
in front of cabinet for residential to dual cylinder unit, for
door opening or when necessary, remove door with quick
release pin. (Combo unit and dual cylinder unit have remov-
able doors, residential does not.)
Photo B
Leveling
Screws
NOTE: Drain Pipe
is NOT an air gap fitting.
The humidifier must never be located outside or where it
may be exposed to freezing temperatures unless a heated,
ventilated weather proof enclosure by others is provided.
Do not mount humidifiers on a hot or vibrating surface.
Table 1 - MAXIMUM OPERATING WEIGHT
Fasten the mounting bracket to wood studs or solid wood
using fasteners shown in fastener recommendation below.
Place the mounting flange on the humidifier cabinet over
the mounting bracket. A sheet metal screw should be
installed through the back of the humidifier cabinet to
secure the humidifier to the mounting bracket. Fasteners
are not provided by Carnes.
Table 2 - FASTENER RECOMMENDATION*
*1/4" Lag Screw, 1" Minimum Length
WATER SUPPLY CONNECTION
Use ordinary tap water (20 to 120 psi) - DO NOT use
hot water, DI (deionized water), RO (reverse osmosis)
water. Using mechanically softened water, or tap water
with conductivity over 800 Micromhos is not recom-
mended. A 3/8" FPT fitting is provided at the bottom of the
humidifier for connection to tap water supply (top of humid-
ifier for HRAA). A shutoff valve, not provided by Carnes,
must be installed just ahead of this fitting.
DRAIN LINE CONNECTION
1. Locate the drain pipe fitting in accessory bag in unit.
2. Connect the drain pipe fitting to the cabinet drain hole
An air gap fitting
must be included
in drain plumbing
3. Connect the drain pipe fitting to an S or P trap. Use
set-up (non-Carnes
installation).
See picture:
If you wish to purchase
an air gap from Carnes
it is an option.
(690-0176)
5
Model
H_AH
H_DH
H_GH
H_HH
MODEL
H_AH
H_DH
H_GH
H_HH
Have proper tooling available to attach the drain pipe.
on the bottom of the unit (Refer to Photo B).
plumbing material capable of handling hot water. Also,
please include a 1" air gap fitting as part of the drain
plumbing. See Photo B.
Note: If the drain water pump accessory package is
used, follow instructions included with the drain water
pump package.
Pounds
61
72
110
203
FASTENERS REQUIRED
4
4
4
6

Advertisement