Gas Connection - Viessmann Vitodens 300 Instalation Manual

49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Gas connection

A Gas connection
Conversion to other gas
types:
Conversion kit installation
instructions
Supplied By www.heating spares.co Tel. 0161 620 6677
Information regarding operation
with LPG
We recommend the installation of an
external safety solenoid valve when
installing the boiler in rooms below
ground level.
1. Carry out a leak test.
!
Important information
Excessive test pressure
leads to damage to the boi-
ler and gas train.
Max. test pressure
150 mbar. If a higher pres-
sure is required for leak
tests, separate the boiler
and the gas train from the
mains gas supply (undo fit-
tings).
2. Purge the gas supply pipe.
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 300 wb3a-49Vitodens 300 wb3a-66

Table of Contents