4. Installing the refrigerant piping
45° ±2°
Apply refrigerating machine oil over the entire flare seat surface.
Fig. 4-1
A Flare cutting dimensions
Copper pipe O.D.
Flare dimensions
(mm)
øA dimensions (mm)
ø9.52
12.8 - 13.2
ø15.88
19.3 - 19.7
B Flare nut tightening torque
Copper pipe O.D.
Tightening torque
(mm)
ø9.52
ø15.88
A
Fig. 4-2
Copper pipe O.D.
Flare tool for R410A
(mm)
Clutch type
ø9.52 (3/8")
ø15.88 (5/8")
277
120
a
c
20
e
d
b
99
218
h
f
95
22
461
g
i
j
47
20
105
600
l
Fig. 4-3
Be sure to only use the flare nuts that
came with the unit.
Tightening angle
(N·m)
(Guideline)
34 - 42
60˚ - 90˚
66 - 82
30˚ - 60˚
A Die
B Copper pipe
A (mm)
0 - 0.5
0 - 0.5
(mm)
66
k
261
70
260
4.2. Indoor unit (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C or more,
thickness of 12 mm or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam insula-
tion materials (specific gravity of 0.03, thickness of 9 mm or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening
flare nut.
• Use two wrenches to tighten piping connections.
• Use leak detector or soapy water to check for gas leaks after connections are
completed.
• Use refrigerant piping insulation provided to insulate indoor unit connections. Insulate
carefully following shown below.
• Use correct flare nuts meeting the pipe size of the outdoor unit.
Available pipe size
Liquid side
ø9.52
Gas side
ø15.88
Warning:
When installing the unit, securely connect the refrigerant pipes before start-
ing the compressor.
4.3. Refrigerant and drainage pipe locations (Fig. 4-3)
Where knockout holes are indicated, use a saw blade to cut along the groove.
Do not cut the hole larger than the indicated groove.
a Rear surface
b Front surface
c Knockout hole for mounting: 4-10 mm diameter hole
d * knockout hole for connections under the unit
e 120 × 120 knockout hole for connections under the unit
f Indoor/outdoor unit connecting terminals
g Power supply terminals
h Electrical equipment box
I Liquid pipe
j Gas pipe
k Drain pipe outlet diameter ø26 <PVC pipe VP20 connection>
l 140 × 80
Knockout hole for refrigerant and drainage piping and electrical wiring
m 90 × 60
Knockout hole for refrigerant and drainage piping
n 27 mm diameter knockout hole for electrical wiring (there is a similar hole on the left side)
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Psa-rp71kaPsa-rp100kaPsa-rp140kaPsa-rp125ka

Table of Contents