Weil-McLain UltraOil Manual page 39

Oil-fired water boiler
Hide thumbs Also See for UltraOil:
Table of Contents

Advertisement

water boiler
Appendix — Ratings
Boiler
I=B=R
Model
Burner
Number
Capacity
Capacity
GPH #2 Oil
Notes:
UO-3
0.80
0.8 GPH
UO-3
1.00
1.0 GPH
UO-4
1.20
Notes
UO-5
1.40
(1) Based on standard test procedures prescribed by the
United States Department of Energy at combustion
condition of 1.0% CO and –0.0" w.c. breeching
draft.
() Ratings shown are for sea level applications only.
For altitudes above ,000 feet, derate the product
capacity by 4% per 1,000 feet above sea level.
() Net I=B=R ratings are based on net installed radia-
tion of sufficient quantity for the requirements of
the building and nothing need be added for normal
piping and pick-up. Water ratings are based on a
Part number 550-141-986/1005
— Boiler Manual
DOE
CSA
CSA
Heating
Input
Output
MBH
MBH
Btuh
Notes 1, 6
Notes 2, 6
Note 2
98
112
98
122
140
122
146
168
146
172
196
172
Net
Boiler
Shipping
I=B=R
Water
Weight,
Ratings
Content
Approx.
MBH
Gallons
Pounds
Notes 3, 6
85
15.0
636
106
15.0
636
127
18.3
737
150
21.5
852
piping and pick-up allowance of 1.1. An addi-
tional allowance should be made for unusual pip-
ing and pick-up loads. Consult local Weil-McLain
Sales Office.
(4) See page 11 for minimum breeching and chimney
sizing.
() Boiler draft losses are based on operation at 11.%
CO
. Set breeching draft at –0.0 inch water col-

umn.
(6) MBH refers to thousands of Btu per hour.
DOE
DOE
Flue
Seasonal
Conn.
Efficiency
Size
AFUE, %
Note 4
86.5
6"
86.5
6"
86.2
6"
86.5
6"
Draft
Loss
Through
Boiler
Inches w.c.
Note 5
0.000
0.020
0.025
0.040
9