Duct System Installation; Condensate Piping Installation - Carrier 50YDV Installation, Operation And Maintenance Instructions

Residential horizontal & vertical packaged geothermal heat pumps
Table of Contents

Advertisement

R e s i d e n t i a l P a c k a g e d U n i t s - 6 0 H z P u r o n
R e v. : 4 J a n . , 2 0 1 2
Horizontal Installation
Condensate Piping – Horizontal Units
Pitch the unit toward the drain as shown in Figure 2 to
improve the condensate drainage. On small units (less
than 2.5 tons/8.8 kW), insure that unit pitch does not cause
condensate leaks inside the cabinet.
Install condensate trap at each unit with the top of the trap
positioned below the unit condensate drain connection as
shown in Figure 6. Design the depth of the trap (water-seal)
based upon the amount of ESP capability of the blower
(where 2 inches [51mm] of ESP capability requires 2 inches
[51mm] of trap depth). As a general rule, 1-1/2 inch [38mm]
trap depth is the minimum.
Each unit must be installed with its own individual trap and
connection to the condensate line (main) or riser. Provide
a means to fl ush or blow out the condensate line. DO NOT
install units with a common trap and/or vent.
Always vent the condensate line when dirt or air can collect
in the line or a long horizontal drain line is required. Also vent
when large units are working against higher external static
pressure than other units connected to the same condensate
main since this may cause poor drainage for all units on the
line. WHEN A VENT IS INSTALLED IN THE DRAIN LINE, IT
MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION
OF THE CONDENSATE FLOW.

Duct System Installation

The duct system should be sized to handle the design
airfl ow quietly. Refer to Figure 3 for horizontal duct system
details or fi gure 8 for vertical duct system details. A fl exible
connector is recommended for both discharge and return
air duct connections on metal duct systems to eliminate
the transfer of vibration to the duct system. To maximize
sound attenuation of the unit blower, the supply and return
plenums should include internal fi berglass duct liner or be
constructed from ductboard for the fi rst few feet. Application
of the unit to uninsulated ductwork in an unconditioned
space is not recommended, as the unit's performance will be
adversely affected.
8
Figure 6: Horizontal Condensate Connection
*3/4" FPT
* Some units include a painted drain
connection. Using a threaded pipe or
similar device to clear any excess paint
accumulated inside this fitting may
ease final drain line installation.
CAUTION! Ensure condensate line is pitched toward
drain 1/4 inch per ft [21mm per m] of run.
DUCT SYSTEM INSTALLATION
At least one 90° elbow should be included in the supply
duct to reduce air noise. If air noise or excessive air fl ow is
a problem, the blower speed can be changed. For airfl ow
charts, consult specifi cations catalog for the series and
model of the specifi c unit.
If the unit is connected to existing ductwork, a previous
check should have been made to insure that the ductwork
has the capacity to handle the airfl ow required for the unit.
If ducting is too small, as in the replacement of a heating
only system, larger ductwork should be installed. All existing
ductwork should be checked for leaks and repaired as
necessary.
®
Condensate Piping
Trap Depth
1.5" [38mm]
3/4" PVC or
Copper by others
CAUTION!
Vent
Min 1.5"
[38mm]
1/4" per foot
(21mm per m)
drain slope
Rev.: 4/30/10B

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50yeh50yed50ydh50ydd50yevGt-px series ... Show all

Table of Contents